MidNite Solar Integration Guide
REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 6 |
4.2 – Charge Controller Settings
Please review Table 2.0 below for Midnite Solar charge controller program settings. To initiate a factory
reset, hold left & right arrow buttons while turning on Battery Breaker. This is normally only done for initial
setup, as doing so will erase all custom settings.
Table 2.0 - Settings for SimpliPhi PHI 3.8 kWh Batteries w/ Midnite Solar Charge Controller
CHARGE CONTROLLER
PHI 2.9 kWh & 3.8 kWh; 24V / 48V
Setting
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
Charging Source
Source
Solar / Wind / Hydro
Battery Voltage (V)
24 / 48
Charge
Battery Charge Setpoints
Volts
EQ (V)
27.2 / 54.4
27.2 / 54.4
28 / 56
Absorb (V)
27.2 / 54.4
27.2 / 54.4
28 / 56
Float (V)
27 / 54
27 / 54
27 / 54
ChgTime
Absorb (Hrs:Mins)
1 Hour
EQ
0 (Disabled)
T-Comp
Comp (mV/°C/cell)
0 (Disabled)
EQ Comp'd
NO
EQ
Auto EQ
0 (Disabled - shows "Manual interval")
Advanced
Ending Amps
3
(A)
4 / 2
Re-Bulk Voltage (V)
25.3 / 50.6
Limits
Output Amps
1,2
45A per PHI 2.9 24V; 28.5A per PHI 2.9 48V
45A per PHI 3.8 24V; 37.5A per PHI 3.8 48V
Input Amps
1
Size based on input charging source
Min T-Comp
N/A (Disabled)
Max T-Comp
N/A (Disabled)
Mode
Battery Charge Setpoints
On/Off
ON
Mode
Hydro / Solar / Legacy P&O / Wind Track / Dynamic / U-Set Voc%
AUX 1
Manual Off
AUX 2
3
Manual Off
Notes:
• 1. Per PHI battery – Refer to Section 3.0 herein for charge controller PHI battery bank sizing.
• 2. Per PHI battery – These settings are calculated by multiplying the nominal value per each PHI battery times
the # of PHI batteries. For other batteries, refer to the Warranty and Specification Sheet for the specific model.
• 3. End Amps settings only work when the “Midnite Whiz Bang Jr & 500A/50mV shunt” are installed. When the
Whiz Bang Jr is used, Aux 2 is not available for a turn off signal from auxiliary source.
• Levels are typical @ 25°C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles, the PHI battery should be allowed to "rest" 15 minutes in
between.
• Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must to be reassessed. Failure to do so will void the Warranty.