Magnum Energy Integration Guide
REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 9 |
General
10k Cycles
(80% DOD)
5k Cycles
(90% DOD)
3.5k Cycles
(100% DOD)
Disconnect Volts
4
27.2V / 54.4V
02E AC In – SOC
ME-BMK is required for this setting
The 02D AC In – VDC setting is preferred over 02E AC In - SOC
Connect SOC
20%
Disconnect SOC
100%
02F Power Up Always
OFF
03 Charger Setup
03C Battery Type
CC/CV
Max Charge Amps
1
(ADC)
45A per PHI3.8 24V
37.5A per PHI3.8 48V
CV Charge Volts (VDC)
27.2V / 54.4V
CV Chg Done Time
1 Hr
(set to “Hold CV Chg VDC” when generator charging)
CV Chg Done Amps (ADC)
4A / 2A
Max CC/CV Time (Hrs)
12 Hrs
Recharge Volts (VDC)
25.3V / 50.6V
03D Absorb Done Time
CC/CV Controlled
03E Max Charge Rate
3
(%)
45A per PHI3.8 24V (see footnote 3 for % calculation)
37.5A per PHI3.8 48V (see footnote 3 for % calculation)
03F Max Charge Time
CC/CV Controlled
03G Final Charge Stage
CC/CV Controlled
Rebulk Volts (VDC)
25.3V / 50.6V
03H EQ Reminder Days
OFF
Notes:
1. Per PHI 3.8 kWh battery – These setting are calculated by multiplying the nominal per-battery
value times the number of batteries.
2. The maximum programmable setting of 48.8V is below the recommended LBCO setting. To
maintain the batteries at a maximum 80% or 90% DOD, utilize the 02D AC In – VDC setting for
grid backup.
3. Per PHI 3.8 kWh battery and as a percentage of the inverter’s or charge controller’s maximum
charge rating – These settings are calculated by multiplying the nominal per-battery value times
the number of batteries, then divide by the equipment’s maximum charging current.
Battery
Quantity
PHI 3.8 / 24V
(45ADC)
1 x MS4024PAE
charge rate
(105ADC charger)
1 x PT-100
charge rate
(100ADC)
PHI 3.8 / 48V
(37.5ADC)
1 x MS4448PAE
charge rate
(60ADC charger)
1 x PT-100
charge rate
(100ADC)
2
90A
85%
90%
75A
100%
75%
3
135A
100%
100%
112.5A
100%
100%
4
180A
100%
100%
150A
100%
100%
• Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles, the battery should be allowed to "rest" 15
minutes in between
CAUTION: When PHI battery quantities change, the capacity and charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.