Magnum Energy Integration Guide
REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 13 |
4.6 – Recharge Voltage Adjustment
The Recharge setting often acts as the trigger in which a new charge cycle will start. The standard voltage
set point is 50.5V, as per the manual; however, you can adjust this setting to fit the application in which the
battery is being used. The following table shows battery voltage correlated with State of Charge (SOC).
Table 7.0 – Correlating Battery Voltage to State of Charge
SOC
Voltage 48V
Voltage 24V
100%
>52.5
>26.2
95%
51.7
25.9
90%
51.6
25.8
75%
51.4
25.7
50%
51.0
25.5
20%
50.2
25.1
10%
49.5
24.8
0%
48.0
24.0
The following Recharge values are suggested settings for these specific applications:
• Back-Up battery: 51.7/26.2
• Off-Grid: 51.4/25.8