Magnum Energy Integration Guide
REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 11 |
4.4 – Auto Generator Start (AGS) Settings
Verify with Magnum Energy and your generator manufacturer regarding your generator’s compatibility
with Magnum’s AGS device.
SETUP
04 AGS Setup
AGS is required for this setting
Verify AGS-generator compatibility with Magnum / Sensata
04A Gen Run VDC
Start Gen Volts
25.2V / 50.4V
Start Volts Delay
1 min
Stop Gen Volts
4
27.2V / 54.4V
Stop Volts Delay
60 min
04C Gen Run Amps
Prevents batteries from over-discharge (amps) by monitoring the
battery current used to power the inverter loads
Start Gen AC Amps
Refer to Table 2.0.
Start Amps Delay
10 sec
Stop Gen AC Amps
[Start Amps Delay Value] – 1A
Stop Amps Delay
120 sec
4.5 – Battery Monitoring Kit (BMK) Settings
A Battery Monitoring Kit (BMK) is not required for system operation.
SETUP
05 BMK Setup
05A Charge Eff
Auto
05B AmpHour Size
1
[200 - 2500 AH]
151Ah per PHI 3.8 24V (minimum 2 batteries)
75Ah per PHI 3.8 48V (minimum 3 batteries)