Magnum Energy Integration Guide
REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 10 |
4.3 – MPPT Charge Controller Settings
Solar charge controllers must be used in DC coupled systems to regulate the power produced by the PV
array that is delivered to the batteries. Magnum Energy offers one MPPT charge controller, the PT-100,
which is compatible with PHI batteries:
SETUP
06 PT Setup
06A Battery Type
Custom
Absorb Volts
27.2V / 54.4V
Float Volts
27V / 54V
EQ Volts
Set to the same value as Absorb Volts to prevent Equalization
EQ Done Time
N/A
06B Absorb Done Time
1 Hr
Absorb Done Amps
4A / 2A
06C Max Charge Rate
3
(%)
45A per PHI3.8 24V (see footnote 3 for % calculation)
37.5A per PHI3.8 48V (see footnote 3 for % calculation)
06D Max Charge Time
12 Hrs
06E Bulk Start
Daily/SunUp
YES, to set the PT-100 to start a Bulk charge cycle each new day at sun-up
Bulk Start Volts
25.5V / 51V
Bulk Start SOC
50%
ME-BMK is required for this setting
06G PT Alarm
PT controller can be programmed fo a low battery voltage alarm
Notes:
1. Per PHI 3.8 kWh battery – These setting are calculated by multiplying the nominal per-battery
value times the number of batteries.
2. The maximum programmable setting of 48.8V is below the recommended LBCO setting. To
maintain the batteries at a maximum 80% or 90% DOD, utilize the 02D AC In – VDC setting for
grid backup.
3. Per PHI 3.8 kWh battery and as a percentage of the inverter’s or charge controller’s maximum
charge rating – These settings are calculated by multiplying the nominal per-battery value times
the number of batteries, then divide by the equipment’s maximum charging current.
Battery
Quantity
PHI 3.8 / 24V
(45ADC)
1 x MS4024PAE
charge rate
(105ADC charger)
1 x PT-100
charge rate
(100ADC)
PHI 3.8 / 48V
(37.5ADC)
1 x MS4448PAE
charge rate
(60ADC charger)
1 x PT-100
charge rate
(100ADC)
2
90A
85%
90%
75A
100%
75%
3
135A
100%
100%
112.5A
100%
100%
4
180A
100%
100%
150A
100%
100%
• Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles, the battery should be allowed to "rest" 15
minutes in between.
CAUTION: When PHI battery quantities change, the capacity and charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.