Charge Efficiency
95%
SoC when Bulk Finished 95%
Notes:
1.
Per PHI 3.8 Battery These settings are calculated by multiplying the nominal per battery value times the # of
batteries.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes in
between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model.
4.3 Victron BMV-700 Programming Settings
Table 2.0 - Settings for SimpliPhi PHI 3.8 kWh 24V / 48V Battery w/Victron BMV-700 Battery Monitor
Victron BMV-700 Settings
PHI 3.8 kWh 24V / 48V
Quick Start
Battery Capacity
1
(Ah)
151Ah per PHI3.8 24V; (302Ah for 2, 453Ah for 3)
75Ah per PHI3.8 48V; (150Ah for 2, 225Ah for 3)
Charged Voltage (V)
26.5 / 53.2
Tail Current (%)
8 / 4
Charge Detection Time (minutes) 1
Peukert Exponent 1.05
Charge Efficiency Factor (%)
98
Current Threshold (A)
0.1
Time to go Averaging Period (minutes)
3
Notes:
1.
Per PHI 3.8 Battery These settings are calculated by multiplying the nominal per battery value times the # of PHI
Batteries.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes in
between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model.