Victron Energy Integration Guide

SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 12 |
FOR BACKUP ONLY SYSTEM
Color Control GX/Venus GX Settings
Keep Batteries Charged
Mode
Optimized (with BatteryLife)
Control Without Grid Meter
OFF
Inverter AC Output in use
ON
Feed-in Excess Solar charger Power ON
Phase Compensation
ON
Minimum Discharge SoC
3
90%
Actual State of Charge Limit 95%
BatteryLife State
Self-consumption
Limit Charger Power
OFF
Limit Inverter Power OFF
Fronius Zero feed-in
OFF
Fronius Zero feed-in active
No battery specific settings
Grid setpoint
50W
Notes:
1.
Per PHI 3.8 Battery These settings are calculated by multiplying the nominal per battery value times the # of PHI Batteries.
2.
These levels exceed the warrantied recommended operating conditions.
3.
For BACKUP ONLY applications, set to desired backup level. This is the level batteries cycle to normally before recharge. If the
grid fails, cut-off is determined by the Dynamic Cut-Off values.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes in between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model.