Table 8.0 – Settings for SimpliPhi PHI Battery w/ OutBack MATE3s AGS
AGS Setup
AGS Enabled
Y
to enable the AGS mode
Port Identifies the HUB port (1-10) for the device that is going to control the
gen
Fault Time The amount of time the generator is given to connect before an AGS Fault
message appears and a fault is logged in the system
Control (Radian inverters only) Selects which terminals will be used for AGS: AUX Output or AUX Relay
Warm Up Time Individual to the specific generator
Coll Down Time Individual to the specific generator
DC Generator Y if a DC Generator is used
AGS Voltage Start
51.2V
nom
PHI Battery
25.6V
nom
PHI Battery
12.8V
nom
PHI Battery
24 Hour Start Disable
N
2 Hour Start Disable
N
2 Minute Start
Enable
Y,
minimum values below (correlate with 80% DoD)
50.4V 25.2V 12.6V
AGS Load Start
Enabled Enable
Y
when necessary (refer to application described below)
Start (kW)
1
1.9 kW per PHI 3.8-51.2V
nom
model battery
1.1 kW per PHI 3.8-25.6V
nom
battery
1.5 kW per PHI 2.9-51.2V
nom
model battery
1.1 kW per PHI 2.9-25.6V
nom
model battery
0.7 kW per PHI 1.4-25.6V
nom
model battery
0.5 kW per PHI 1.4-12.8V
nom
model battery
0.3 kW per PHI 730-25.6V
nom
model battery
0.3 kW per PHI 730-12.8V
nom
model battery
Start Delay Varies depending on the characteristics of the loads.
~0-1 minutes can be used.
Stop (kW) Varies depending on the characteristics of the loads.
The Start kW minus 100 Watts can be used but may need adjustment.
Stop Delay Varies depending on the characteristics of the loads.
~0-1 minutes can be used.
Notes:
1. Per PHI Battery – These settings are calculated by multiplying the per-battery kW value times the # of batteries. Refer to
Table 2.0 – MAX Continuous Charge Rate per Battery (Watts DC) and convert Watts to kiloWatts for legacy battery
specifications.
• Levels are typical @ 25°C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles the battery should be allowed to “rest” 15 minutes in between.