Outback Power Integration Guide
Table Of Contents
REV042920
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 13 |
programming battery charging settings via the MATE3s are posted here:
https://www.youtube.com/watch?v=RDsLpuSDG7o
. (
Note:
This video shows inverter/charger programming; make
sure to also program charge controller settings by selecting
Charge Controller
in the
Settings
menu.)
The following Table outlines settings for the Radian and FXR/VFXR inverters, not the SkyBox.
Table 1.0 – Settings for PHI Batteries with OutBack Inverters Based on 80% DoD Levels
Inverter Settings
> Battery Charging
51.2V
nom
PHI Battery
25.6V
nom
PHI Battery
12.8V
nom
PHI Battery
Absorb Voltage
when Generator Charging or AC
Coupled PV Charging
56V 28V 14V
Absorb Voltage
when Grid Charging
54.4V 27.2V 13.6V
Absorb Time
when Generator Charging or AC
Coupled PV Charging
0.1 hours
Absorb Time
when Grid Charging
2 hours
Float Voltage
N/A
(54V / 27V / 13.5V may be used as a placeholder value, but Float is disabled
by setting Float Time to 0)
Re-Bulk Voltage 50.8V 25.4V 12.7V
Float Time 0 Hours
Re-Float Voltage
N/A
(50V / 25V / 12.5V may be used as a placeholder value, but Float is disabled
by setting Float Time to 0)
EQ Voltage
N/A
(54.4V / 27.2V / 13.6V may be used as a placeholder value, but EQ is disabled
by setting EQ Time to 0)
EQ Time 0 Hours
> Battery Protection
Low Battery Cut-Out Voltage
1
50V 25V 12.5V
Low Battery Cut-Out Delay
130 seconds
Low Battery Cut-In Voltage
52V 26V 13V
High Battery Cut-Out Voltage
60V 30V 15V
High Battery Cut-Out Delay
1 second
High Battery Cut-In Voltage
54V 27V 13.5V
> Mini Grid
Mini Grid Connect to Grid
Refer to Section 4.2.1
Mini Grid Delay