SimpliPhi Battery Manual
Table Of Contents
- PHI 3.8-MTM Battery Models
- and gain control of your own power.
- SimpliPhi Power helps you manage your power as a personal resource.
- power generation source – solar, wind, generator – on or off grid, and protects your home and mission-critical business functions from power outages and
- constraints, toxic coolants and the risk of thermal runaway. Safe lithium ferrous phosphate (LFP). No cobalt. No toxic hazards.
- (BMS) to create a portfolio of high performance, scalable and enduring energy storage solutions that provide power security, resilience and daily cycling for savings on your utility bill – all with a 98% efficiency rate.
- Table of Contents
- 1.0 – Introduction
- 2.0 – Safety
- 3.0 – Pre-Installation
- 4.0 – Installation
- 5.0 – Programming
- 6.0 – Troubleshooting
- Appendix A – PHI Battery Safety & Green Attributes,
- Appendix B – PHI Battery Bank Sizing Guide
- Appendix C – PHI Approved External Chargers
- Appendix D – PHI Legacy Battery Parameters
SIMPLIPHIPOWER.COM | 805-640-6700
REV202203161300
15
© SIMPLIPHI POWER, INC.
CAUTION: Do not attempt to loosen the large brass nut at the base of the terminals; doing so will damage the
PHI battery and Void the Warranty.
MISE EN GARDE: Ne pas desserrer le gros écrou en laiton à la base des bornes; cela endommagerait la
Batterie PHI et Annulerait la Garantie.
4.5 – PHI Battery Connection Terminals
4.5.1 – Batteries with Threaded Studs
The PHI 3.8-M Battery is equipped with two 3/8’’ (10 mm) threaded studs with a lock washer and nut. The red colored
high temperature molded insert connection is for the positive lead. The black colored high temperature insert connection
is for the negative lead.
Water Resistant Cable Boots are also included and will be in place when your units arrive. The boots are to be placed over
the cable terminations and will stretch to form a water-resistant seal around the base of the molded inserts and terminal
connections.
4.5.2 – Torque Value for Batteries with Threaded Studs
PHI Batteries with threaded stud terminals have a torque specification of 160 in-lbs. (13.3 ft-lbs.).
Figure 3.0 – PHI 3.8-M Threaded Stud
Threaded Studs = 3/8” (10mm)
Torque Value = 160 in-lbs
CAUTION:
Using an impact driver or power tools on the terminals will Void the Warranty. Using power tools
or impact drivers may damage the terminal even if it doesn’t result in breakage. Only use accurately calibrated
and properly adjusted torque wrenches when tightening terminal hardware.
MISE EN GARDE
: L'utilisation d'un tournevis à percussion ou d'outils électriques sur les bornes annulera la
garantie. L'utilisation d'outils électriques ou de tournevis à percussion peut endommager le terminal même
s'il n'en résulte pas de rupture. Utilisez uniquement des clés dynamométriques correctement calibrées et
correctement ajustées lors du serrage du matériel de la borne.