4. To wire the Battery Monitor’s pre-scaler board to the battery bank:
a. Do not connect the orange wire (Va1+) or the yellow wire (Va2-). Including these wires in
the pre-scaler-to-battery connection will result in inaccurate Battery Monitor SoC
calculations.
b. Wire the twisted pair (violet wire 1- and blue wire I+) to the battery shunt. Notice
connection points A and B as outlined in the Battery Monitor Quickstart Guide
:
c. The pre-scaler’s grey wire (Vm-) and black wire (V-) connect to the DC negative busbar
paralleling the batteries in the PHI battery bank.
d. The pre-scaler’s brown wire (Vm+) and red wire (V+) connect to the DC positive busbar
paralleling the batteries in the PHI battery bank.
5. Do not connect the Battery Temperature Sensor; the PHI batteries’ charging regimen does not
involve any temperature compensation.
to battery DC
Negative
Busbar