Schneider Electric Integration Guide

REV20201
222
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 6 |
CAUTION: If a firmware update is executed on Schneider Electric equipment, ALL the
settings must be reverified. The programmed settings shown in the following tables must be
applied based on desired Warranty/Cycle life. The recommended is 80% depth of discharge.
4.2 – Inverter/Charger Settings
The Conext XW+ Inverter/Charger has a firmware limitation that creates a potential issue with Lithium-Ion
batteries: the Low Battery Cut-Out Voltage (LBCO) setting is limited to 48V maximum. This value is below the
recommended LBCO settings to maximize cycle-life of most Lithium-Ion batteries including PHI batteries. Per
the Warranty, a 48V LBCO corresponds to 100% DoD and maintains a much more limited cycle life.
Until Schneider Electric releases updated firmware to adjust this setting above 48V, this issue can be largely
mitigated by setting the “Recharge Volts” above the desired LBCO thresholds as outlined in Table 1.0 below.
Therefore, systems that do not rely solely on renewable energy (i.e. grid tied systems, AGS systems) will
typically start charging the batteries once the recharge voltage level is reached, preventing further discharge of
the batteries and thus optimizing cycle-life.
Table 1.0 Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Schneider Conext XW Pro & XW+ Inverters
Conext XW+ & XW Pro Settings
Advanced Settings > Inverter Settings
Low Battery Cut Out Voltage
1
48
LBCO Hysteresis
2.0V
LBCO Delay
10 Sec
High Batt Cut Out
60V
Search Watts
Default
Search Delay
Default
Charger Settings > Custom Settings
Batt Type
Custom
Lithium Ion
Control 2StgNoFloat
Bulk Voltage
56V
MaxBulkCurrent (C/2)
2
37.5A (per PHI 3.8)
DisChgImax
2
80A (per PHI 3.8) (up to 500A per bank)
DisChgImax Timer 300 sec
Batt Capacity
2
75Ah (per PHI 3.8)
Max Charge Rate (C/2)
2,3
37.5A (per PHI 3.8)
Default Batt Temp
Warm
Recharge Volts 50.4V
Absorb Time
.1 Hour (6 minutes)
Chg Block Start Default
Chg Block Stop
Default
Notes:
1.
Maximum setting of 48V limited by some inverter firmware is below the recommended setting.
2.
Per PHI 3.8 kWh 48V battery These settings are calculated by multiplying the nominal value per-battery value times
the # of batteries. For other batteries, refer to the Warranty and Specification Sheet for the specific model. Refer to
Charge Controller Bank Sizing under the “Battery Bank Sizing” section.
3.
To calculate Max Bulk Current as a percentage, divide the calculated Max Bulk Current in Amps DC by the equipment’s
maximum potential charging current: