Outback Power Integration Guide

SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 13 |
programming battery charging settings via the MATE3s are posted here:
https://www.youtube.com/watch?v=RDsLpuSDG7o
. (
Note:
This video shows inverter/charger programming; make
sure to also program charge controller settings by selecting
Charge Controller
in the
Settings
menu.)
The following Table outlines settings for the Radian and FXR/VFXR inverters, not the SkyBox.
Table 1.0 Settings for PHI Batteries with OutBack Inverters Based on 80% DoD Levels
Inverter Settings
> Battery Charging
51.2V
nom
PHI Battery
25.6V
nom
PHI Battery
12.8V
nom
PHI Battery
Absorb Voltage
56V 28V 14V
Absorb Time
0.1 hours
Float Voltage
N/A
(54V / 27V / 13.5V may be used as a placeholder value, but Float is disabled
by setting Float Time to 0)
Re-Bulk Voltage 50.8V 25.4V 12.7V
Float Time 0 Hours
Re-Float Voltage
N/A
(50V / 25V / 12.5V may be used as a placeholder value, but Float is disabled
by setting Float Time to 0)
EQ Voltage
N/A
(54.4V / 27.2V / 13.6V may be used as a placeholder value, but EQ is disabled
by setting EQ Time to 0)
EQ Time 0 Hours
> Battery Protection
Low Battery Cut-Out Voltage
1
50V 25V 12.5V
Low Battery Cut-Out Delay
130 seconds
Low Battery Cut-In Voltage
52V 26V 13V
High Battery Cut-Out Voltage
60V 30V 15V
High Battery Cut-Out Delay
1 second
High Battery Cut-In Voltage
54V 27V 13.5V
> Mini Grid
Mini Grid Connect to Grid
Refer to Section 4.2.1
Mini Grid Delay
REV20220523