Magnum Energy Integration Guide
Table Of Contents
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 8 |
4.0 – Program Settings for PHI Batteries
In order to maintain the Warranty, it is critical to ensure that the appropriate settings for the desired Warranty
are programmed in all of the system components. This section will cover the basic concepts and settings for
Magnum Energy equipment.
4.1 – Depth of Discharge
In order to optimize your system’s and your PHI batteries’ performance and life, SimpliPhi Power recommends
programming the equipment settings to maintain the batteries at a maximum 80% Depth of Discharge (DOD).
This will enable the batteries to achieve an expected 10,000 cycles.
Greater DOD is possible but will result in reduced cycle life. To maintain a maximum 80% DOD using Magnum
equipment, a backup grid connection or standby generator (with Magnum Auto Generator Start device) is
required. .
CAUTION:
If a firmware update is executed on Magnum Energy equipment, ALL the settings must
be re-verified. The programmed settings shown in the following tables must be applied based on
desired Warranty/cycle life. 80% Depth of Discharge is recommended.
4.2 – Inverter Settings
General
80% DOD
90% DOD
100% DOD
MS4024 / MS4448 Inverter
ME-ARC & ME-RTR
Remote Control
CTRL
01 AC In Control
AC In Control Auto Connect
Auto Connect if AC power source is a generator
VDC Connect if AC power source is the grid
02 CHG Control Multi-Stage
03 Gen Control AGS is required for this setting
04 PT Control PT-100 charge controller is required for this setting
SETUP
01 System Setup
01D Max Charge Amps
CC/CV Controlled
Displayed once “CC/CV” is selected in 03C Battery Type menu
01E Link PT CHG Settings NO
02 Inverter Setup
for 80% DOD for 90% DOD 100% DOD
02B Low Batt CutOut
2
- LBCO (VDC) 24.4V / 48.8V 24.4V / 48.8V 24V / 48V
02C AC In - Time
IF
you want to connect to grid power at a pre-determined time of day
Connect Time
The time each day that the incoming AC source connects and powers the loads
Disconnect Time
The time that the AC source disconnects and no longer powers the loads
02D AC In - VDC Grid power connection is required for this setting