4.6 – Recharge Voltage Adjustment
The Recharge setting often acts as the trigger in which a new charge cycle will start. The standard voltage set
point is 50.5V, as per the manual; however, you can adjust this setting to fit the application in which the battery
is being used. The following table shows battery voltage correlated with State of Charge (SOC).
Table 7.0 – Correlating Battery Voltage to State of Charge
SOC
Voltage 48V
Voltage 24V
100% >52.5 >26.2
95% 51.7 25.9
90% 51.6 25.8
75% 51.4 25.7
50% 51.0 25.5
20% 50.2 25.1
10% 49.5 24.8
0% 48.0 24.0
The following Recharge values are suggested settings for these specific applications:
• Back-Up battery: 51.7/26.2
• Off-Grid: 51.4/25.8