Table 2.0 – 04C Gen Run Amps
04C Gen Run Amps auto starts the generator based on the amount of AC amps needed to handle the load the
inverter is running.
A battery bank with a maximum continuous discharge rate greater than the inverter’s load rate does not need
to utilize the
04C Gen Run Amps setting.
For example, 4 x PHI 3.8 48V batteries paired with 1 x Magnum MS 4448 PAE run no risk of over-discharging
to power the
instantaneous load:
• Max. continuous discharge current for 4 x PHI 3.8 48V = 4 x 37.5A = 150ADC
o 150A x 48V = 7,200 WDC
• Assuming inverter efficiency is 94%*, WattsAC = WDC ÷ 0.94
o 7,200 WDC ÷ 0.94 = 7,660 WAC
• 1 x Magnum 4448 PAE inverter has a continuous power rating of 4,000 WAC, and a 5 second
surge power rating of 5,800 WAC
o 7,660 W > 5,800 W
o The 4 batteries have a higher instantaneous power rating than the inverter
Conversion from DC to AC Gen Run Amps for 1 to 5 PHI 3.8 kWh 24V Batteries
A
B
C
D
E
F
# of Parallel
Batteries
DC Current
Limit
ADC x VDC (24)
WDC ÷ Inverter Efficiency
(93% = .93)
Column D ÷ Inverter
Voltage
(120 or 240 VAC,
dep. on inverter; 240
VAC used below)
Round down
(programmable
range = 5 - 60A)
1
45A
1,080 WDC
1,161 WAC
4.8 AAC
2
90A 2,160 WDC 2,323 WAC 9.7 AAC
9 AAC
3
135A 3,240 WDC 3,484 WAC 14.5 AAC
14 AAC
4
180A 4,320 WDC 4,645 WAC 19.4 AAC
19 AAC
5
225A 5,400 WDC 5,806 WAC 24.2 AAC
24 AAC
*The Magnum MS4024PAE has a peak inverter efficiency of 93%.
Conversion from DC to AC Gen Run Amps for 1 to 5 PHI 3.8 kWh 48V Batteries
A
B
C
D
E
F
# of Parallel
Batteries
DC Current
Limit
ADC x VDC (48)
WDC ÷ Inverter
Efficiency (94% = 0.94)
olumn D ÷ Inverter Voltage
(120 or 240 VAC,
dep. on inverter; 240 VAC
used below)
Round down
(only whole #s can
be used as input)
1
37.5A 1,800 WDC 1,915 WAC 8 AAC
8 AAC
2
75A 3,600 WDC 3,830 WAC 16 AAC
16 AAC
3
112.5A 5,400 WDC 5,745 WAC 23.9 AAC
23 AAC
4
150A 7,200 WDC 7,660 WAC 31.9 AAC
31 AAC
5
187.5A 9,000 WDC 9,574 WAC 39.9 AAC
39 AAC
*The Magnum MS4448PAE has a peak inverter efficiency of 94%.