4.3 – MPPT Charge Controller Settings
Solar charge controllers must be used in DC coupled systems to regulate the power produced by the PV array
that is delivered to the batteries. Magnum Energy offers one MPPT charge controller, the PT-100, which is
compatible with PHI batteries:
SETUP
06 PT Setup
06A Battery Type Custom
Absorb Volts 28V / 56V
Float Volts 27V / 54V
EQ Volts Set to the same value as Absorb Volts to prevent Equalization
EQ Done Time N/A
06B Absorb Done Time . (6 Minutes)
Absorb Done Amps
2% of the PHI Battery bank’s capacity
06C Max Charge Rate
3
(%)
75A
per PHI3.8 24V (see footnote 3 for % calculation)
37.5A
per PHI3.8 48V (see footnote 3 for % calculation)
06D Max Charge Time 12 Hrs.
06E Bulk Start
Daily/SunUp YES, to set the PT-100 to start a Bulk charge cycle each new day at sun-up
Bulk Start Volts 25.5V / 51V
Bulk Start SOC
50%
ME-BMK is required for this setting
06G PT Alarm PT controller can be programmed for a low battery voltage alarm
Notes:
1.
Per PHI 3.8 kWh battery – These settings are calculated by multiplying the nominal per-battery value
times the number of batteries.
2.
The maximum programmable setting of 48.8V is below the recommended LBCO setting. To maintain
the batteries at a maximum 80% or 90% DOD, utilize the
02D AC In – VDC
setting for grid backup.
3.
Per PHI 3.8 kWh battery and as a percentage of the inverter’s or charge controller’s maximum charge
rating – These settings are calculated by multiplying the nominal per-battery value times the number
of batteries, then divide by the equipment’s maximum charging current.
Battery
Quantity
PHI 3.8 /
24V
(45ADC)
1 x MS4024PAE
charge rate
(105ADC charger)
1 x PT-100
charge rate
(100ADC)
PHI 3.8 / 48V
(37.5ADC)
1 x MS4448PAE
charge rate
(60ADC charger)
1 x PT-100
charge rate
(100ADC)
2
150A
100%
90%
75A
100%
75%
3
225A
100%
100%
112.5A
100%
100%
4
300A
100%
100%
150A
100%
100%
• Levels are typical @ 25C and may need adjusting at temperature extremes.
•
When performing rapid deep charge/discharge cycles, the battery should be allowed to "rest" 15 minutes in
between.
CAUTION:
When PHI battery quantities change, the capacity and charge/discharge current
settings must be reassessed. Failure to do so will void the Warranty.