Victron Energy Integration Guide
REV050918
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 9 |
4.2 – PHI 3.5 General Settings with Victron
The general program settings for the PHI 3.5 Batteries with Victron products are outlined below.
Table 1.0 - Settings for SimpliPhi PHI 3.5 kWh 24V / 48V Battery w/Victron
General
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
Battery Curve Fixed
Capacity
1
(Ah)
138Ah
per PHI3.5 24V; (
276Ah
for 2,
414Ah
for 3)
69Ah
per PHI3.5 48V; (
138Ah
for 2,
207Ah
for 3)
Absorb Voltage (V) 28 / 56 28.8 / 57.6 28.8 / 57.6
Absorb Time 6 Minutes
Float Voltage (V) 27 / 54 (typically Disable)
Discharge Voltage "LBCO" (V) 25.1 / 50.2 24.8 / 49.6 24 / 48
Re-Charge (V) 25.3 / 50.6
Max Discharge/Charge Current (C/2)
1
45A
per PHI3.5 24V; (
90A
for 2,
135A
for 3)
34A
per PHI3.5 48V; (
68A
for 2,
102A
for 3)
Peukert Expo 1.05
Charge Efficiency 95%
SoC when Bulk Finished 95%
Notes:
1. Per PHI 3.5 Battery – These settings are calculated by multiplying the nominal per battery value times the #
of batteries.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes
in between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model.
4.3 – Victron BMV-700 Programming Settings
Table 2.0 - Settings for SimpliPhi PHI 3.5 kWh 48V Battery w/Victron BMV-700 Battery Monitor
Victron BMV-700 Settings PHI 3.5 kWh 24V / 48V
Quick Start
Battery Capacity
1
(Ah)
138Ah per PHI3.5 24V; (276Ah for 2, 414Ah for 3)
69Ah per PHI3.5 48V; (138Ah for 2, 207Ah for 3)
Charged Voltage (V) 26.5 / 53.2
Tail Current (%) 4
Charge Detection Time (minutes) 1
Peukert Exponent 1.05
Charge Efficiency Factor (%) 98
Current Threshold (A) 0.1
Time to go Averaging Period (minutes) 3
Notes:
1. Per PHI 3.5 Battery – These settings are calculated by multiplying the nominal per battery value times the #
of PHI Batteries.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes
in between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model.
CAUTION: When battery quantities change, the capacity current settings must to be reassessed.