Victron Energy Integration Guide
REV050918
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 10 |
4.4 – Inverter / Charger Settings
The program settings for the PHI 3.5 Batteries with Victron Inverter / Charger products are outlined below.
Table 3.0 - Settings for SimpliPhi PHI 3.5 kWh 48V Battery w/Victron Inverter / Charger
Program Settings for SimpliPhi Model 3.5 - 48V with Victron Inverters / Chargers
Phoenix VE.Direct Inverters
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
Victron Connect
Static Low Voltage Cutoff
Output Voltage 230V
Output Frequency 50Hz
Dynamic Cutoff OFF
Low Battery Shutdown 50.2 49.6V 48V
Low Battery Restart & Alarm 54V
Charge Detect 54V
ECO Mode Wake-up Minimum Power 15W
ECO Mode Search Interval 2.5S
Victron Connect
Dynamic Low Voltage Cutoff
Enable Dynamic Cutoff ON
Battery Type Custom
Battery Capacity
1
34A per PHI3.5; (68A for 2, 102A for 3)
Voltage for Discharge 0A 50.2 49.6V 48V
Voltage for Discharge 8A 50.2 49.6V 48V
Voltage for Discharge 23A 50.2 49.6V 48V
Voltage for Discharge 66A
2
50
49.1V
47.5V
MultiPlus & Quattro
Inverter Chargers
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
VE Configure
General Tab
SoC when Bulk Finished 95%
Total Battery Capacity
1
69Ah per PHI3.5; (138Ah for 2, 207Ah for 3)
Charge Efficiency 95%
VE Configure
Inverter Tab
DC Input Low Shut-Down 50.2 49.6V 48V
DC Input Low Restart 50.5V
DC Input Low Pre-Alarm 51V
VE Configure Charger Tab
Battery Type Lithium
Lithium > Yes Lithium Iron Phosphate
Absorb Voltage 56V 57.6V 57.6V
Float Voltage 54V
Charge Current (C/2)
1
34A per PHI3.5; (68A for 2, 102A for 3)
Repeated Absorb Time 1.00 Hr
Repeated Absorb Interval 7 Days
Absorb Time 0.10 Hour (6 Minutes)
Notes:
1. Per PHI 3.5 Battery – These settings are calculated by multiplying the nominal per battery value times the # of
batteries.
2. These levels exceed the warrantied recommended operating conditions.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes in
between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model.