Schneider Electric Integration Guide
REV0226
18
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 8 |
Table 3.0 - Settings for SimpliPhi PHI 3.5 kWh 48V Battery w/Schneider Conext Battery Monitor
Conext Battery Monitor Settings
Setting
Value
Capacity
2
69Ah (per PHI 3.5)
Discharge Rate
20 Hrs
Nominal Temp
67F
Shunt Amps
500
Shunt mV
50
Self Disch
<1%/Month
Discharge Floor
20%
Float Voltage
53.32
Float Amps
2%
Auto Sync Time
240 Sec
Temp Unit
Celsius
Back Light Timer
30 Sec
Peukert Expo
1.05
Charge Eff Mode
Automatic
Temp Coeff
0.5Ah/degC
Default Temp
76 Deg F
Sync Sensitivity
5
Time Rem Filter
Faster
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.
5.0 – Specifications & Warranty
For your reference:
• See PHI 3.5 kWh 48V Specifications Sheet.
• See PHI 3.5 kWh 48V 10-Year Warranty; Failure to adhere to installation protocol will void
Warranty.
6.0 – SimpliPhi Technical Support
For technical support related to your PHI 3.5 kWh 48V Battery (or other SimpliPhi Power products),
please contact us directly at:
805.640.1874
techsupport@simpliphipower.com