Outback Power Integration Guide
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com |
SimpliPhiPower.com
| 7 |
REV101918
4.4 – FLEXnet DC Settings
Table 3.0 - Settings for SimpliPhi PHI 3.5 kWh 48V Battery w/Outback FLEXnet DC
FLEXnet DC Settings
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
FNDC Battery Ah
1
138Ah / 69Ah
FNDC Charge Voltage (V) 27.6 / 55.2 28.2 / 57 28.2 / 57
FNDC Charged Return Amps 8A / 4A
FNDC Battery Charge Factor 98%
FNDC Relay Invert Logic No
FNDC Relay Voltage High/Low High = 26.5/53, Low = 28.8/49.6
FNDC Relay SOC High/Low SOC High = 0%, SOC Low = 0%
FNDC Relay Delay High = 1, Low = 0
Notes:
1. Per PHI 3.5 kWh battery – These settings are calculated by multiplying the nominal per battery value
times the # of batteries. Refer to Charge Controller Bank Sizing under the “Battery Bank Sizing” section.
Levels are typical @25C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the battery should be allowed to “rest” 15 minutes in
between.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.
4.5 – MATE3/MATE3s Settings
Table 4.0 - Program Settings for SimpliPhi PHI 3.5 kWh 48V Battery w/Outback MATE3/MATE3s
MATE3 / MATE3s Settings
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
FLEXnet DC Advanced Control Low SOC Warning = 20%
FLEXnet DC Advanced Control Critical SOC Warning = 10%
Notes:
Levels are typical @ 25C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in
between.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.