General
10k Cycles
(80% DOD)
5k Cycles
(90% DOD)
3.5k Cycles
(100% DOD)
02E AC In - SOC Disconnect SOC (%) 100
02F Power Up Always
OFF
03 Charger Setup
03A AC Input
1
(A)
45A per PHI3.5 24V
34A
per PHI3.5 48V
03B VAC Dropout
Set as applicable
03C Battery Type
CC/CV
Max Charge
1
(A)
45A per PHI3.5 24V
34A
per PHI3.5 48V
CV Charge (V)
28 / 56
CV Charge Done
Amps
DoneAmps (A)
4 / 2
MaxTime (Hrs) 12
Recharge (V)
25.3 / 50.6
03D Absorb Done
If “CC/CV” has been selected as battery type, “CC/CV
Controlled” is displayed
Time (Hrs)
0.1
Amps (A)
4 / 2
SOC
4
(%)
100
03E Max Charge Rate
5
(%)
45A per PHI 3.5 24V (as a percentage)
34A per PHI 3.5 48V (as a percentage)
03F Max Charge Time (Hrs)
12
If “CC/CV” has been selected as battery type, “CC/CV
Controlled” is displayed
03G Final Charge Stage
Multi, Rebulk 25.3 / 50.6
If “CC/CV” has been selected as battery type, “CC/CV
Controlled” is displayed
03H EQ Reminder Days
OFF
If “CC/CV” has been selected as battery type, “CC/CV
Controlled” is displayed
04 AGS Setup
OFF (if used set as follows)
04A Gen Run VDC
Start Gen Volts = 25.2 / 50.4
Start Volts Delay = 15 min.
Stop Gen Volts = Float for full battery charge or set to
specific voltage for partial battery charge
Stop Volts Delay = 0 sec (if Stop Gen Volts = Float)
04C Gen Run Amps1
5
(A)
Refer to Table 6.0
04F Max Gen Run Time
12 Hrs
05 BMK Setup
05A Charge Eff (%) 99
05B AmpHour Size
138Ah per PHI3.5 24V
(3 minimum = 414Ah)
69Ah per PHI3.5 48V
(3 minimum = 207Ah)