Magnum Energy Integration Guide
REV1128
18
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 8 |
General
10k Cycles
(80% DOD)
5k Cycles
(90% DOD)
3.5k Cycles
(100% DOD)
09 Final Charge - Final Multi
Rebulk (v)
25.3 / 50.6
10 Pwr Up Always - Pwr Up
NO
Notes:
• 1. Per PHI 3.5 kWh battery – These setting are calculated by multiplying the nominal per-battery
value times the number of batteries.
•
2. The maximum value of the low battery cut out (LBCO) is 24.4/48.8 V.
•
3. Calculate this value as a percentage of the inverter/charger’s maximum charging current.
•
Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles, the battery should be allowed to "rest" 15
minutes in between.
CAUTION: When PHI battery quantities change, the capacity and charge/discharge current
settings must be reassessed. Failure to do so will void the Warranty.
Table 2.0 – Program Settings for SimpliPhi PHI 3.5 – 24V/48V Battery w/Magnum General Settings
General
10k Cycles
(80% DOD)
5k Cycles
(90% DOD)
3.5k Cycles
(100% DOD)
MS4024 / MS4448 Inverter
ME-ARC Remote Control
CTRL
01 ACIn Control
Auto-Connect
02 CHG Control Multi-Stage
03 Gen Control
OFF (refer to manual if optional ME-AGS-N used)
04 PT Control
04A PT CHG Ctrl
Multi-Stage
04B PT Aux Relay Ctrl
DISENGAGE (can be used if desired)
04C PT Alarm Control
OFF, Enable Test, Enable w/QT
04D PT MPPT Sweep 15 Min Sweep
METER
01 System Setup
01D Max Charge Amps
1
(A)
“CC/CV Controlled” will be displayed on this menu’s screen
once “CC/CV” is selected as the battery type from the 03C
Battery Type menu.
01E Link PT CHG Settings
YES if using a PT-100, NO if not using a PT-100
02 Invert Setup
02A Search Watts
OFF
02B LBCO Setting
2
(V)
25.1 / 50.2
24.8 / 49.6
24 / 48
02D AC In - VDC Connect Volts (V)
25.3 / 50.6
02D AC In - VDC Disconnect Volts (V) 28 / 56
02E AC In - SOC Connect SOC
3
(%)
80