Magnum Energy Integration Guide
REV1128
18
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 6 |
3.2 – Charge Calculation: Charge Controller Power Sizing
To optimize solar harvesting, a properly sized PHI battery bank should be able to accept the maximum
PV charge current. To determine the minimum number of PHI batteries required to optimize PV, divide
the output of the charge controller(s) by the “max continuous charge current” per PHI battery. Be sure to
verify the “max continuous charge current” for the PHI battery model that you’re using, because it may
differ from C/2 depending on the model.
Charge Example
This example uses the following calculation:
B
#PV
≥ I
PVChrgMax
/ I
BatChrgMax
This example assumes the following:
• Max. continuous charge current for PHI 3.5 48V = 34A
• PV charge controller max = 100A
The calculation and assumptions correspond to:
B
#PV
≥ 100A/34A = 2.94
In this example, a properly sized PHI battery bank based on the available PV charge has a
minimum of 3 batteries. This maximizes the use of available PV while ensuring the batteries are never
stressed by overcharging. If the PHI battery bank has fewer batteries than calculated, configure the
inverter settings to limit the charge rate below the specified rating of the PHI battery. These settings are
described in the following sections of this Integration Guide.
In summary: When comparing the same system using these two calculations to size the PHI
battery bank, the minimum number of batteries should be the greater of the Discharge Calculation
& Charge Calculation results.