Magnum Energy Integration Guide

REV1128
18
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 13 |
Parameters
Setting
04I Gen No-Load Time
Consult your generator manufacturer for generator's Warm
Up
and
Cooldown
time.
04J Gen 100% SOC
Not needed for LFP batteries.
05 BMK Setup
05A Charge Efficiency
05B Battery Amp Hrs Size
138 / 69 per battery
07 PT Setup
07A Battery Type
CC/CV
Two-stage charging cycle
Max Chg Rate
45 / 34 per battery. Calculated as a percentage of the
inverter's Max Charger Output.
CV Chg Volts
27.7 / 55.4
CV Charge Done Time
0.1 Hrs:
Max Time = 1 hr
DC Volts to Recharge = 25.3 / 50.6
CV Charge Done Amps
Do not use; see "Info" on pg. 34 of the Magnum RTR
manual.
Hold CV Chg Volts
Never hold CV Chg Voltsfor LFP batteries.
07B Absorb Done
CC/CV controlled
07C Max Charge
CC/CV controlled
07D Bulk Start
Daily/SunUp
YES or NO, depending on whether you want the PT-100 to
charge the batteries daily.
Low VDC
25.5 / 51
SOC
OFF
Table 6.0 – Gen Run Amps
Number of Parallel Batteries
Amps at 240 VAC
Amps at 120 VAC
PHI 3.5/24V Batteries
1
5
10
2
10
20
3
15
30
4
20
40
5
25
50
6
30
60
PHI 3.5/48V Batteries
1
7
15
2
15
30
3
22
45
4
30
60
5
37
75
6
45
90