Magnum Energy Integration Guide
REV1128
18
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 12 |
Parameters
Setting
when DC is Connected
02G Inverter Threshold to Start
Parallel
60% (default)
03 Charger Setup
03A AC Input Amps
Set to match the current rating of the utility power or the
generator's circuit breaker.
03B Low VAC Dropout
AC1 = 80, AC2 = 70 (default)
03C Battery Type
CC/CV
2-stage charging cycle
Max Chg Amps
45 / 34 per battery
CV Chg Volts
27.7 / 55.4
CV Charge Done Time
0.1 hrs:
• Max Time = 1 hr
• DC Volts to Recharge = 25.3 / 50.6
CV Charge Done Amps
Do not use; see "Info" on page 34 of the Magnum RTR
manual.
Hold CV Chg Volts
Never hold CV chg volts for LFP batteries.
03D Absorb Done
CC/CV controlled
03E Max Charge
CC/CV controlled
03F Final Charge Stage
CC/CV controlled
03G Days to remind when to EQ
CC/CV controlled
04 AGS Setup
04A Gen Run DC Volts
Start Volts
25.2 / 50.4
Stop Volts
25.7 / 51.4. Or to allow the battery bank to go through a full
bulk and absorption charge, set to
Float (Silent)
.
Start Delay
10 s. Increase if generator is nuisance starting.
Stop Delay
5 min.
04B Gen Run Time
Runs generator at a set time each day
(e.g., while at work
each day to have charged batteries when you get home
without having to hear it run).
04C Gen Run AC Amps
Start AC Amps
Ensures that batteries do not over-discharge. Set “Gen Run
AC Amps” according to Table 6.0.
Start Delay
0 sec.
Stop AC Amps
Set to 1A less than the “Start AC Amps” value.
Stop Delay
Depends on loads:
• Increase delay time if loads greater than Start AC Amps
value come on and off frequently.
•
Otherwise, use the default setting.
04D Gen Run SOC
Do not use; 04A setting is more accurate.
04E Gen Run Temp
Runs the generator when temperature increases.
04F Max Gen Run Time
Sets the maximum time the generator will run if autostarted.
04G Gen Quiet Time
Sets the period of time each day in which the generator is
not allowed to run automatically.
04H Gen Exercise
Exercises the generator if it has not been operated for a
period of time.