SimpliPhi Battery Manual
Table Of Contents
- 1.0 – Introduction
- 2.0 – Safety
- 2.0 – Pre-Installation
- 4.0 – Installation
- 5.0 – Programming
- 6.0 – Troubleshooting
- Appendix A – PHI Battery Safety & Green Attributes, Certifications
- Appendix B – PHI Battery Bank Sizing Guide
- Appendix C – PHI Approved External Chargers
- Appendix D – PHI Legacy Battery Parameters
REV202010211307© SIMPLIPHI POWER, INC.
SIMPLIPHIPOWER.COM | 805-640-6700
30
Appendix B – PHI Battery Bank Sizing Guide
48V Sizing for Maximum Instantaneous Discharge (Load Rate)
PHI 3.8 -
51.2V
nom
PHI 3.8 -
25.6V
nom
PHI 1.4 -
25.6V
nom
PHI 730 -
25.6Vnom
PHI 1.4 -
12.8Vnom
PHI 730 -
12.8V
nom
Max Continuous
Dis/charge Rate
(ADC)
37.5 75 28.5 14 40 28.5
Max Continuous
Dis/charge Rate
(kW DC)
1.92 1.92 0.7296 0.3584 0.512 0.3648
Inverter Make / Model
Inverter Power Rating
(kW AC)
Inverter Efciency Load Rate (kW DC)
PHI 3.8 - 51.2Vnom
Minimum Battery
Quantity
Magnum MS 4448 4.4 94% 4.7 3
Magnum MS 4048 4 94% 4.3 3
OutBack Radian 8048A 8 93% 8.6 5
OutBack Radian 4048A 4 93% 4.3 3
OutBack SkyBox 5 97% 5.2 3
OutBack VFXR 3648A 3.6 93% 3.9 3
OutBack FXR 3048A 3 93% 3.2 2
OutBack GVFX 3648
(discontinued)
3.6 93% 3.9 3
OutBack GTFX 3048
(discontinued)
3 93% 3.2 2
Schneider XW Pro 6.8 93% 7.3 4
Schneider XW+ 6848 6.8 92.5% 7.4 4
Schneider XW+ 5548 5.5 93% 5.9 4
Schneider SW 4048 4 94% 4.3 3
Selectronic SP PRO SPMC
481-AU
5 96% 5.2 3
Selectronic SP PRO SPMC
482-AU
7.5 96% 7.8 5
Sol-Ark-8K 8 96.5% 8.3 5
Sol-Ark-12K 12 96% 12.5 7
Victron Quattro
48/3000/35
3 94% 3.2 2
Victron Quattro
48/5000/70
5 95% 5.3 3
Victron Quattro
48/10000/140
10 96% 10.4 6
Victron Quattro
48/15000/200 (230 VAC)
15 96% 15.6 9