SimpliPhi Battery Manual

Table Of Contents
REV202010211307© SIMPLIPHI POWER, INC.
SIMPLIPHIPOWER.COM | 805-640-6700
26
SOC 12V 24V 48V
100% > 13.13 VDC > 26.25 VDC > 52.5 VDC
95% 12.93 25.9 VDC 51.7 VDC
90% 12.91 25.8 VDC 51.65 VDC
75% 12.85 25.7 VDC 51.4 VDC
50% 12.75 25.5 VDC 51.0 VDC
20% 12.55 25.1 VDC 50.2 VDC
10% 12.38 24.8 VDC 49.5 VDC
0% 12.0 24.0 VDC 48.0 VDC
Table 5.0 – Optimal Operation Parameters
MISE EN GARDE: Avant la mise en service du système, le contrôleur et l’onduleur doivent être programmés
conformément aux recommandations du fabricant avec les réglages appropriés. Consultez les manuels
du fabricant et/ou les Guides d’Intégration indiqués sur la page internet de la Documentation Produit de
SimpliPhi (Schneider, Magnum, Outback, etc.). Ne pas respecter ces instructions endommagera les Batteries
PHI Annulera la Garantie.
les tableaux d’Intégration du Contrôleur de Charge sont uniquement fournis à titre d’exemple.
CAUTION: Before commissioning the system, the appropriate controller and inverter settings must be
programmed per the manufacturer’s recommendations. Consult the manufacturer’s manuals and/or the
Integration Guides listed on SimpliPhi’s Product Documentation web page (Schneider, Magnum, Outback,
etc.). Failing to do so will damage the PHI batteries and will Void the Warranty. The following Charge
Controller Integration tables are for general reference only.
6.0 – Troubleshooting
If your PHI Battery bank is reaching its Low Battery Cut Out voltage (LBCO), load disconnects or load shedding set points may
need to be adjusted.
The PHI batteries are reading extremely low or no voltage:
Programmed settings in the PHI Battery’s accompanying Balance of System equipment should prevent the PHI Battery’s internal
BMS from reaching its low voltage setting. However, in the instance that the PHI Battery’s BMS has turned the PHI battery off,
the battery will read low or no voltage, and the following steps should be taken to re-set the BMS:
1. Turn off each of the built-in breakers in all of the PHI Batteries in the battery bank*.
2. Turn off the main DC disconnect located in the inverter’s power panel, between the battery bank and the inverter.
3. Turn off the main breaker at the top of the inverter’s AC distribution panel or sub-panel.
4. Wait 5 minutes, for the BMS in each battery to re-set itself.
5. Use a multi meter to take voltage measurements of each PHI battery in the battery bank, to make sure the voltage increased
to the minimum voltage necessary for the inverter to turn on.
To measure a single battery’s voltage within a battery bank, only the battery being measured has its built-in breaker in the
ON (I) position; all other batteries in the bank must have their built-in breakers OFF (0).
6. Turn on each of the built-in breakers in all of the PHI Batteries in the battery bank.
7. Turn on the main DC disconnect located in the inverter’s power panel.