Recommended Operating Conditions for 10 Year Warranty
Equivalent to 80% Retained Capacity 10,000 cycles 5,000 cycles 3,500 cycles
Depth of Discharge (DoD) 80% 90% 100%
Operating Temperature °F (°C) 32 to 120 (0 to 49)
Programming Settings for Ancillary
Equipment
12V 24V 48V 12v 24V 48V 12V 24V 48V
Low Battery Cut-Off Voltage (V) 12.6 25.1 50.2 12.4 24.8 49.6 12 24 48
Absorb / Charging Voltage
12V 24V 48V
14V 28V 56V
Absorb Time 6 minutes (0.1 Hours)
Absorb End Amps (if applicable) 2% of the PHI Battery bank’s total Ah capacity
Notes / Operating Limitations for PHI Batteries
PHI 3.8 PHI 1.4 PHI 730
Limitations by Model 48V 24V 24V 12V 24V 12V 12V 24V 48V
Continuous Discharge Rate (ADC) 37.5 75 28.5 40 14 28.5 12 24 48
Surge Discharge Rate (ADC) –
10 minutes maximum
80 25 50
Continuous Charge Rate (ADC) 37.5 75 28.5 40 14 28.5 12 24 48
5.0 – Programming
5.1 – Operating Parameters Related to Cycle Life
To maintain optimal PHI Battery health and longevity, adhere to the operating parameters outlined in Tables 5.0 and 6.0 below.
Refer to the manufacturer-specic Integration Guide from SimpliPhi’s Product Documentation web page for a complete list of
settings: https://simpliphipower.com/product-documentation/.
Table 5.0 – Optimal Operation Parameters
Table 6.0 – Operating Limitations
Levels are typically @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to “rest” 15 mins in between.
Although the PHI battery charges to the voltages outlined above, the battery “rests” at approximately 13.3V / 26.7V / 53.3V.
Refer to Table 6.0 below for a complete Battery Voltage versus State of Charge (SOC) gauge.