MISE EN GARDE: Les Batteries SimpliPhi doivent fonctionner en accord avec une programmation appropriée
du Système Equilibré. Un fonctionnement des batteries avec un équipement qui na pas été programmé selon
les paramètres spéciés par Simpliphi endommagera les Batteries PHI et Annulera la Garantie.
MISE EN GARDE: Charger les batteries à une température inférieure à 0° C (32° F) Annulera la Garantie.
CAUTION: SimpliPhi Batteries must operate in conjunction with properly programmed Balance of System
equipment. Operating the batteries with equipment that has not been programmed to SimpliPhi’s specied
parameters will damage the PHI batteries and Void the Warranty
CAUTION: Remember that charging the batteries in sub-freezing conditions will Void the Warranty.
8. Conrm all loads are turned OFF. Disconnect the inverter’s AC Output breaker or turn off the breaker at the top of your
loads’ breaker panel.
9. The main DC disconnect in the inverter’s power panel should still be in the OFF position.
10. Turn all battery circuit breaker switches to the ON (I) position.
11. Turn the main DC disconnect in the inverter’s power panel ON.
12. At this point, the inverter may come on automatically in standby mode, or the inverter might need to be manually turned on.
13. Program the Balance of System Equipment (inverter and/or charge controller) to SimpliPhi’s settings, as specied in the
relevant Integration Guide (https://simpliphipower.com/product-documentation/) and generally outlined in Section 5.0 –
Programming of this Manual.
14. Charge the batteries fully. When rst commissioning the battery system, the batteries must be charged fully before
connecting any loads. Neglecting to charge the batteries fully when rst commissioning the battery system will Void the
Warranty.
15. Battery charging may be accomplished via the inverter/charger using an AC power source such as the grid or a generator, or
via a charge controller using power from a connected solar PV array.
16. The batteries will bulk charge to 56 VDC / 28 VDC / 14 VDC, will Absorb for 6 minutes (0.1 hours), and will then rest at
approximately 53.3 VDC / 26.7 VDC / 13.3 VDC. At this point in the charging cycle, these voltages (53.3V / 26.7V / 13.3v)
are considered 100% SOC.
17. Once the batteries are fully charged, turn on the inverter’s AC Output breaker and/or the breaker at the top of your loads’
breaker panel.
MISE EN GARDE: Tous les produits SimpliPhi Power Core Power et Peak Power sont conçus pour fonctionner
exclusivement en parallèle. Ne jamais les connecter en série pour obtenir une tension plus élevée. Le câblage
en série détruira les Batteries PHI et Annulera la Garantie.
Vérier la polarité de tous les branchements avant de mettre le système sous tension. Une polarité inverse
aux bornes de la Batterie PHI détruira les batteries PHI et Annulera la Garantie.