PHI Series Battery Wiring Guide

Table Of Contents
REV052720
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 2 |
Storage Capacity and total available Amperage is increased incrementally with the number of units wired in
Parallel. For example, two PHI 3.8 kWh-51.2V
nominal
(75Ah) Batteries wired in parallel are rated at a combined 7.6
total kWh, 51.2 Volts DC and 150Ah. Each PHI 3.8 kWh-51.2V
nominal
Battery also has a maximum continuous
discharge rate of 37.5 Amps DC and paralleling two of these batteries incrementally increases the maximum
continuous charge and discharge rate. The two paralleled PHI 3.8 kWh-51.2V
nominal
batteries have a combined
maximum continuous charge and discharge rate of 75 Amps DC (2 × 37.5ADC).
5.0 – PHI Battery Parallel Wiring Methods
Parallel wiring can be accomplished in one of two ways:
1.
Method #1: Pairs of battery cables (one positive, one negative) connect between each PHI Battery in the
battery bank and the positive and negative DC busbars, plates, or terminal blocks. If the DC busbars,
plates, or terminal blocks are located somewhere other than the paired inverter’s power panel (diagramed
in Figure 1.0), additional connections may be required between a battery combiner box or terminal blocks
and the Balance of System (BoS) equipment (see Figure 2.0). Refer to Sections 6.0 and 6.1 of this Guide
for further instruction.
Figure 1.0 - Four PHI Batteries Paralleled in a Schneider Conext Power Distribution Panel (PDP)