PHI Series Battery Wiring Guide

Table Of Contents
REV052720
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 13 |
Example 2: Examine Figure 2.0 and assume the following in this example regarding the 12-PHI 3.8kWh-
48V battery bank.
Assume: DC Loads = 0 Watts, Two Conext XW+ 5548 inverters are used with AC Power Rating = 5,500
W each and efficiency of 93%, Inverter Charger Rating = 110 ADC per inverter, and two MPPT Charge
Controllers are used each with Maximum Output = 80 ADC.
1. Maximum current liable to be drawn from the battery bank
    =
2 × 5,500 
0.93
+
(
0 
)
= 11,828 
   =
11,828 
48 
= 246.4 
2. Maximum current potentially charging the battery bank
The Conext XW+5548 includes a 110A charger; two inverters in parallel have a combined charge rate of
220ADC. The two MPPT 80 charge controllers have a combined maximum output of only 160ADC, so
the larger 220ADC figure is the maximum current potentially charging the battery bank.
3. The greater of the two values is used to size the cables.
Because 246.4 ADC is greater than 220ADC, the 246.4 ADC figure is used to size the battery
cables. The battery cables from the battery combiner box to the inverters are sized according to the
246.4 ADC ampacity rating. From each individual battery to the battery combiner box:
246.4 
12   
= 20.53 
4. From these calculations, conclude that:
The battery combiner box must be rated to 246.4 ADC or greater. Therefore, the MidNite
Lithium Battery Combiner Box (link here
), rated at 250 ADC, is appropriate.
The twelve positive and twelve negative battery-to-combiner box cables are rated to handle at
least 20.53 ADC. Refer to the NEC’s Table 310.15(B)(16) and in this example assume a
THHN/THWN-2 (90°C insulation) copper conductor is used to choose a minimum
14 AWG size
cable.
The single positive and single negative combiner box-to-inverters cables are rated to handle at
least 246.4 ADC. Refer to the NEC’s Table 310.15(B)(16) and assume a THHN/THWN-2 (90°C
insulation) copper conductor is used to choose a
4/0 AWG size cable.