PHI Series Battery Wiring Guide

Table Of Contents
REV052720
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com| SimpliPhiPower.com
| 10 |
Helpful Tips:
SimpliPhi’s two-PHI battery busbars (SKU #BB-2) with a 50°C rise are rated at 455 ADC. Positive (red)
and negative (black) busbars measure 9.37” x 1” x 3/16”.
SimpliPhi’s three-PHI battery busbars (SKU #BB-3) with a 50°C rise are rated at 455 ADC. Positive (red)
busbars measure 21.5” x 1” x 3/16” and negative (black) busbars measure 19.5” x 1” x 3/16”.
CAUTION: Again, no material (such as a washer) should be placed between the current
carrying terminal and the interconnecting busbars. The interconnecting busbars are placed on
the PHI Batteries’ terminals first, then the flat washer, lock washer, and nut are secured to
the terminal posts.
CAUTION: Do not reverse polarity. Use a voltmeter to check polarity before making
connections to the battery terminals. Reversing polarity will Void the Warranty.
9.0 – Battery Bank Expansion
All equations in Section 6.0 must be reconsidered when adding new PHI batteries to an existing SimpliPhi battery
bank. If there is a chance that the battery bank may be expanded upon in the future, consider upfront the
appropriate battery cable, battery busbar, terminal block or DC busbar ratings required for the eventual battery
bank.