AmpliPHI Sol-Ark Integration Guide
Table Of Contents
- 1.0 – Introduction
- 2.0 – Battery Bank-to-Inverter Connection
- 3.0 – Battery Bank Sizing
- AmpliPHI 3.8 Battery
- 3.8 kWh DC @ 100% DoD
- Rated kWh Capacity per Battery
- 3.04 kWh DC @ 80% DoD (recommended)
- 37.5 Amps DC (1.9 kW DC)
- MAX Continuous Discharge Rate
- 4.0 – Program Settings for PHI Batteries
- 5.0 – Use Cases & Application Notes
- 6.0 – Specifications & Warranty
- 7.0 – SimpliPhi Power Technical Support
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
|
12
|
© SIMPLIPHI POWER
Table 1 – Sol-Ark Battery Settings for AmpliPHI Battery Models
System Setup > Battery Setup
for your reference
AmpliPHI
> Batt Tab
BMS Lithium Batt Manually check this box
Batt Capacity 75 Ah per AmpliPHI 3.8 battery
BMS handles SOC determination.
No manual programming needed
Max A Charge
1,2
≤37.5 ADC per PHI 3.8 battery (Lower
charge rates improve battery life)
BMS auto-populates Max A Charge.
No manual programming needed.
Max A Discharge
1
≤37.5 ADC per PHI 3.8 battery
BMS auto-populates Max A Discharge. No
manual programming needed.
TEMPCO 0 mv/C/Cell (disabled)
BMS auto-populates TEMPCO.
No manual programming needed.
Use Batt V Charged not checked
Use Batt % Charged Manually check this box
No Battery not checked
Activate Battery do not check this box
> Charge Tab
Start V
Use Start % instead of Start V when using
Batt % Charged instead of Batt V Charged (in the Batt tab)
Start %
3
80% DoD – 21%
90% DoD – 11%
100% DoD – 1%
A
1,4
≤37.5 ADC per AmpliPHI 3.8 battery
BMS auto-populates Charge A.
Lower charge rates improve battery life,
which can be manually set)
Gen Charge / Grid Charge
5
Check the Gen Charge box when a generator is connected to the Gen Input breaker.
Check the Grid Charge box when a generator is connected to the Grid Input breaker,
or when a grid connection is utilized to charge the batteries.
Float V 54 V
BMS auto-populates this setting.
No manual programming is needed.
Absorption V
6
56 V
BMS auto-populates this setting.
No manual programming is needed.
Equalization V
7
56 V BMS auto-populates this setting.
30 days No manual programming is needed.
2 hours
> Discharge Tab
Shutdown
80% DoD – 20% (50.2 V) 80% DoD – 20%
90% DoD – 10% (49.5 V) 90% DoD – 10%
100% DoD – 0% (48 V) 100% DoD – 0%
Low Batt
80% DoD – 30% (50.5 V) 80% DoD – 30 %
90% DoD – 20% (50.2 V) 90% DoD – 20%
100% DoD – 10% (49.5 V) 100% DoD – 10%
Restart >1% Greater than the programmed Low Batt Value
Batt Resistance Resistance mOhms = 24 ÷ (PHI 3.8 battery quantity)