AmpliPHI 3.8kWh Battery Installation Manual

1.3.3 Networking Communications Cables & Plugs
Each AmpliPHI battery comes with a 4’ CAT5 cable, a terminator plug, and an RJ45 dust cover for
networking communication set-up (explained in greater detail in Section 4.7 Communications
Wiring).
1.4 – Specifications
Please review Table 1.0 below for AmpliPHI Battery specifications, including physical dimensions, Warranty
period, and technical data.
Table 1.0 - AmpliPHI Battery Specifications
AmpliPHI 3.8™ (51.2V
nominal
) AmpliPHI 3.8™ Internal BMS
DC Voltages - Nominal 51.2 VDC Programmed Absorb Voltage 56 VDC
Amp-Hours 75 Ah Programmed Float Voltage 54 VDC
Rated Capacity
3.8 kWh DC at 100% DoD
3.04kWh DC @ 80% DoD
Over-Voltage Fault Trip
2
60 VDC
MAX Discharge Rate
(10 minutes)
100 Amps DC
(5.1 kW DC)
Low-Voltage Fault Trip
2
45 VDC
MAX Continuous
Discharge & Charge Rate
37.5 Amps DC
(1.9 kW DC)
Programmed Discharge & Charge Rate
per battery
2
37.5 Amps DC
(1.9 kW DC)
DC Voltage Range
1
48 to 56 VDC
Depth of Discharge
1
up to 100%
Charging Low Temperature Fault Trip
2
32° F (0° C)
Charging Temperature
1
32° to 120° F (0° to 49° C) Discharging Low Temperature Fault Trip
3
-4° F (-20° C)
Operating Temperature
1
-4° to 140° F (-20° to 60° C) High Temperature Fault Trip
3
158° F (70° C)
Storage Temperature
6 months: 14° to 77° F (-10° to 25° C)
3 months: - to 113° F (-20° to 45° C)
Self-Discharge Rate
< 1% per month (with battery off)
Memory Effect None Maximum Quantity of Networked Batteries 40
Cycle Life 10,000+ cycles (@ 80% DoD) Networking Cable CAT5 or
t
Warranty Period 10 Years Networking Port RJ45
Weight
Dimensions (W x H x D)
13.5 x 14 x 8 in.
(15.5” H w/terminals) / 0.88 ft
3
(34.3 x 35.6 x 20.3 cm / 0.025 m
3
)
Notes:
1
Max operating ranges. Operating outside of these conditions will Void your Warranty.
2
These AmpliPHI BMS Fault Trip conditions result
in the need for the BMS to be re-set manually (refer to
Section 6.0 - Troubleshooting of this Manual)
3
These AmpliPHI BMS Fault Trip conditions result in automatic BMS reconnection when fault conditions are
no longer detected. There is no need to re-set the BMS manually in these instances.
Specifications are typical/nominal. Subject to change without notice.