AmpliPHI Sol-Ark Integration Guide
Table Of Contents
- 1. introduction
- 2. PHI battery bank-to-inverter connection
- Wire the PHI Battery bank to the Sol-Ark according to the PHI Battery Installation Manual, not according to the Sol-Ark Manual:
- Figure 1 โ Sol-Ark to Battery Connection
- It is acceptable but not required to use the ferrite choke on the positive and negative DC busbar-to-inverter leads (see Figure 1 above).
- SimpliPhi and Sol-Ark recommend against using the 100 Ohm resistor included with the Sol-Ark equipment to charge the Sol-Arkโs capacitors when connecting the PHI Batteries for the first time (as described in the Sol-Ark Install Guide Ownerโs Manual).
- Do not install the Battery Temperature Sensor. The PHI Batteries require no temperature compensation.
- 3. Battery bank sizing
- A properly sized PHI battery bank is sized to prevent over-discharge and over-charge from accompanying equipment. While the programming features of the Sol-Ark allow for battery discharging and charging according to specifically set parameters (refer ...
- Therefore, the PHI battery bank should still be sized to protect against over-discharge. In the case of an AC Coupled system setup, the PHI battery bank should also be sized to protect against over-charge from the solar photovoltaic (PV) array. In a D...
- Discharge Example: ,๐ฉ-#๐ฐ๐๐.โฅ,,๐ฐ๐๐-๐๐พ.รท,๐ฐ๐๐-๐๐๐.-,๐ฉ๐๐-๐๐พ..
- Charge Example: ,๐ฉ-#๐ท๐ฝ.โฅ,,๐ท๐ฝ-๐๐พ.-๐.๐ร,๐ฉ๐๐-๐๐พ..
- ๏ท AC Coupled Solar PV Array is rated at 8 kW
- ๏ท PHI 3.8 kWh-51.2Vnom battery has a maximum continuous charge rate of 1.92 kWDC
- ,๐ฉ-#๐ท๐ฝ.โฅ,,๐-๐๐พ.-๐.๐ร,๐.๐๐-๐๐พ..=๐.๐
- A properly sized PHI battery bank based on the maximum charge from the AC Coupled solar PV array has a minimum of 6 batteries. This ensures that the battery bank does not over-charge from the AC Coupled solar PV.
- When comparing the same system using both the discharge and charge calculations for sizing the PHI battery bank, the minimum number of batteries in the bank should be the greater of the two results. For instance, when examining the discharge calculati...
- While the PHI battery bankโs charge rate in a DC Coupled system can be limited via Sol-Ark programming (Max A Charge), consider the PHI battery bankโs maximum continuous charge rate in the systemโs design.
- Charge Example: ,๐ฉ-#๐ท๐ฝ.โฅ,,๐ท๐ฝ-๐๐พ.ร,๐ฐ๐๐-๐๐๐.-,๐ฉ๐๐-๐๐พ..
- ๏ท DC Coupled Solar PV Array is rated at 8 kW
- ๏ท Sol-Ark PV-to-Battery efficiency is 97.5%
- ๏ท PHI 3.8 kWh-51.2Vnom battery has a maximum continuous charge rate of 1.92 kWDC
- ,๐ฉ-#๐ท๐ฝ.โฅ,,๐-๐๐พ.ร,๐.๐๐๐-๐๐๐.-,๐.๐๐-๐๐พ..=๐.๐๐
- A PHI battery bank utilizing the entire DC Coupled solar PV output potential has 5 batteries. However, programming the Max A Charge in the Sol-Ark to 150 A (4 ร 37.5 ADC) would prevent the over-charging of a battery bank that includes only 4 batteries...
- Homeowners with little to no loads on during the day (while solar power production is at its peak) might consider sizing a larger PHI battery bank to take advantage of the entire solar PV output potential for battery charging. Homeowners that consiste...
- 4. program settings for phi batteries
- 5. USE CASES & Application notes
- Sol-Ark equipment includes many advanced programming features and a variety of modes (more than one mode can be used simultaneously). This section of the Guide will outline the system programming and setup basics for common use cases. However, refer a...
- 6. SPECIFICATIONS & WARRANTY
- For your reference:
- ๏ท See PHI 3.8 kWh Specifications Sheet.
- ๏ท See PHI 2.9 kWh Specifications Sheet.
- ๏ท See PHI Battery 10 Year Limited Warranty.
- Failure to adhere to installation protocol will void the Warranty.
- 7. SIMPLIPHI TECHNICAL SUPPORT
- For technical support related to your PHI Battery (or other SimpliPhi Power products), please contact us directly at:
- 805.640.6700
- techsupport@simpliphipower.com
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 4 |
3. BATTERY BANK SIZING
A properly sized PHI battery bank is sized to prevent over-discharge and over-charge from accompanying
equipment. While the programming features of the Sol-Ark allow for battery discharging and charging
according to specifically set parameters (refer to Section 4 of this Guide), the Sol-Ark does not limit the
batteriesโ maximum discharge current (
Max A Discharge) in an off-grid or grid-failure scenario.
Therefore, the PHI battery bank should still be sized to protect against over-discharge. In the case of an AC
Coupled system setup, the PHI battery bank should also be sized to protect against over-charge from the solar
photovoltaic (PV) array. In a DC Coupled system, the PHI battery bankโs charge rate can be limited via Sol-Ark
equipment programming (
Max A Charge). When sizing the PHI battery bank according to both the discharge
and charge criteria, use the greater of the two calculation results as the minimum quantity of PHI batteries in
the bank.
Discharge Calculation: Inverter Power Bank Sizing
To protect against over-discharge (voiding the battery Warranty), the PHI battery bank should be sized so that
the inverterโs load rate does not exceed the batteriesโ maximum continuous discharge rate.
The discharge calculation uses the nomenclature below:
โข Battery maximum continuous discharge rate (kW
DC
) = Bat
kW
(typically @ C/2)
= (maximum battery discharge current ร battery voltage nominal)
โข Inverter power full load (โload rateโ) = Inv
kW
โข Inverter DC-to-AC efficiency = Inv
eff
Discharge Example: ๎นฎ
#๎นต๎บ๎บ
โฅ
๎นต๎บ๎บ
๎บ๎บ
รท๎นต๎บ๎บ
๎บ๎บ๎บ
๎นฎ๎บ๎บ
๎บ๎บ
โข Sol-Ark-8K inverter is rated at 8 kW
o Depending on the Sol-Arkโs mode of operation (refer to Section 5 of this Guide), the inverter
may power only loads on the critical loads sub-panel or it might power loads both on the
critical loads sub-panel and the main house breaker panel. Consider the inverterโs mode when
sizing the battery bank according to โload rate.โ
โข Sol-Ark-8K inverter DC-to-AC efficiency is 95.5%
โข PHI 3.8 kWh-51.2V
nom
battery has a maximum continuous discharge rate of 1.92 kW
DC
๎ดค
#๏๏ก๏ฉ
โฅ
8
๏๏
รท 0.955
๏๏๏
1.92
๏๏
= 4.4
A properly sized PHI battery bank based on the maximum discharge of the inverter, or load rate, has a minimum
of 5 batteries. This ensures that the battery bank does not over-discharge to power the loads. Refer to this
Section 5 of this Guide to verify battery bank sizing in specific use cases.