AmpliPHI Sol-Ark Integration Guide

Table Of Contents
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 4 |
3. BATTERY BANK SIZING
A properly sized PHI battery bank is sized to prevent over-discharge and over-charge from accompanying
equipment. While the programming features of the Sol-Ark allow for battery discharging and charging
according to specifically set parameters (refer to Section 4 of this Guide), the Sol-Ark does not limit the
batteriesโ€™ maximum discharge current (
Max A Discharge) in an off-grid or grid-failure scenario.
Therefore, the PHI battery bank should still be sized to protect against over-discharge. In the case of an AC
Coupled system setup, the PHI battery bank should also be sized to protect against over-charge from the solar
photovoltaic (PV) array. In a DC Coupled system, the PHI battery bankโ€™s charge rate can be limited via Sol-Ark
equipment programming (
Max A Charge). When sizing the PHI battery bank according to both the discharge
and charge criteria, use the greater of the two calculation results as the minimum quantity of PHI batteries in
the bank.
Discharge Calculation: Inverter Power Bank Sizing
To protect against over-discharge (voiding the battery Warranty), the PHI battery bank should be sized so that
the inverterโ€™s load rate does not exceed the batteriesโ€™ maximum continuous discharge rate.
The discharge calculation uses the nomenclature below:
โ€ข Battery maximum continuous discharge rate (kW
DC
) = Bat
kW
(typically @ C/2)
= (maximum battery discharge current ร— battery voltage nominal)
โ€ข Inverter power full load (โ€œload rateโ€) = Inv
kW
โ€ข Inverter DC-to-AC efficiency = Inv
eff
Discharge Example: ๎นฎ
#๎นต๎บ”๎บœ
โ‰ฅ
๎นต๎บ”๎บœ
๎บ‘๎บƒ
รท๎นต๎บ”๎บœ
๎บ‹๎บŒ๎บŒ
๎นฎ๎บ‡๎บš
๎บ‘๎บƒ
โ€ข Sol-Ark-8K inverter is rated at 8 kW
o Depending on the Sol-Arkโ€™s mode of operation (refer to Section 5 of this Guide), the inverter
may power only loads on the critical loads sub-panel or it might power loads both on the
critical loads sub-panel and the main house breaker panel. Consider the inverterโ€™s mode when
sizing the battery bank according to โ€œload rate.โ€
โ€ข Sol-Ark-8K inverter DC-to-AC efficiency is 95.5%
โ€ข PHI 3.8 kWh-51.2V
nom
battery has a maximum continuous discharge rate of 1.92 kW
DC
๎ดค
#๏‡‚๏‡ก๏‡ฉ
โ‰ฅ
8
๏‡ž๏‡
รท 0.955
๏‡˜๏‡™๏‡™
1.92
๏‡ž๏‡
= 4.4
A properly sized PHI battery bank based on the maximum discharge of the inverter, or load rate, has a minimum
of 5 batteries. This ensures that the battery bank does not over-discharge to power the loads. Refer to this
Section 5 of this Guide to verify battery bank sizing in specific use cases.