AmpliPHI Sol-Ark Integration Guide

Table Of Contents
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 3 |
2. PHI BATTERY BANK-TO-INVERTER CONNECTION
Wire the PHI Battery bank to the Sol-Ark according to the PHI Battery Installation Manual, not according to
the Sol-Ark Manual:
Figure 1 – Sol-Ark to Battery Connection
It is acceptable but not required to use the ferrite choke on the positive and negative DC busbar-to-inverter
leads (see Figure 1 above).
SimpliPhi and Sol-Ark recommend against using the 100 Ohm resistor included with the Sol-Ark equipment to
charge the Sol-Ark’s capacitors when connecting the PHI Batteries for the first time (as described in the
Sol-
Ark Install Guide Owner’s Manual).
Do not install the Battery Temperature Sensor. The PHI Batteries require no temperature compensation.