AmpliPHI Sol-Ark Integration Guide
Table Of Contents
- 1. introduction
- 2. PHI battery bank-to-inverter connection
- Wire the PHI Battery bank to the Sol-Ark according to the PHI Battery Installation Manual, not according to the Sol-Ark Manual:
- Figure 1 โ Sol-Ark to Battery Connection
- It is acceptable but not required to use the ferrite choke on the positive and negative DC busbar-to-inverter leads (see Figure 1 above).
- SimpliPhi and Sol-Ark recommend against using the 100 Ohm resistor included with the Sol-Ark equipment to charge the Sol-Arkโs capacitors when connecting the PHI Batteries for the first time (as described in the Sol-Ark Install Guide Ownerโs Manual).
- Do not install the Battery Temperature Sensor. The PHI Batteries require no temperature compensation.
- 3. Battery bank sizing
- A properly sized PHI battery bank is sized to prevent over-discharge and over-charge from accompanying equipment. While the programming features of the Sol-Ark allow for battery discharging and charging according to specifically set parameters (refer ...
- Therefore, the PHI battery bank should still be sized to protect against over-discharge. In the case of an AC Coupled system setup, the PHI battery bank should also be sized to protect against over-charge from the solar photovoltaic (PV) array. In a D...
- Discharge Example: ,๐ฉ-#๐ฐ๐๐.โฅ,,๐ฐ๐๐-๐๐พ.รท,๐ฐ๐๐-๐๐๐.-,๐ฉ๐๐-๐๐พ..
- Charge Example: ,๐ฉ-#๐ท๐ฝ.โฅ,,๐ท๐ฝ-๐๐พ.-๐.๐ร,๐ฉ๐๐-๐๐พ..
- ๏ท AC Coupled Solar PV Array is rated at 8 kW
- ๏ท PHI 3.8 kWh-51.2Vnom battery has a maximum continuous charge rate of 1.92 kWDC
- ,๐ฉ-#๐ท๐ฝ.โฅ,,๐-๐๐พ.-๐.๐ร,๐.๐๐-๐๐พ..=๐.๐
- A properly sized PHI battery bank based on the maximum charge from the AC Coupled solar PV array has a minimum of 6 batteries. This ensures that the battery bank does not over-charge from the AC Coupled solar PV.
- When comparing the same system using both the discharge and charge calculations for sizing the PHI battery bank, the minimum number of batteries in the bank should be the greater of the two results. For instance, when examining the discharge calculati...
- While the PHI battery bankโs charge rate in a DC Coupled system can be limited via Sol-Ark programming (Max A Charge), consider the PHI battery bankโs maximum continuous charge rate in the systemโs design.
- Charge Example: ,๐ฉ-#๐ท๐ฝ.โฅ,,๐ท๐ฝ-๐๐พ.ร,๐ฐ๐๐-๐๐๐.-,๐ฉ๐๐-๐๐พ..
- ๏ท DC Coupled Solar PV Array is rated at 8 kW
- ๏ท Sol-Ark PV-to-Battery efficiency is 97.5%
- ๏ท PHI 3.8 kWh-51.2Vnom battery has a maximum continuous charge rate of 1.92 kWDC
- ,๐ฉ-#๐ท๐ฝ.โฅ,,๐-๐๐พ.ร,๐.๐๐๐-๐๐๐.-,๐.๐๐-๐๐พ..=๐.๐๐
- A PHI battery bank utilizing the entire DC Coupled solar PV output potential has 5 batteries. However, programming the Max A Charge in the Sol-Ark to 150 A (4 ร 37.5 ADC) would prevent the over-charging of a battery bank that includes only 4 batteries...
- Homeowners with little to no loads on during the day (while solar power production is at its peak) might consider sizing a larger PHI battery bank to take advantage of the entire solar PV output potential for battery charging. Homeowners that consiste...
- 4. program settings for phi batteries
- 5. USE CASES & Application notes
- Sol-Ark equipment includes many advanced programming features and a variety of modes (more than one mode can be used simultaneously). This section of the Guide will outline the system programming and setup basics for common use cases. However, refer a...
- 6. SPECIFICATIONS & WARRANTY
- For your reference:
- ๏ท See PHI 3.8 kWh Specifications Sheet.
- ๏ท See PHI 2.9 kWh Specifications Sheet.
- ๏ท See PHI Battery 10 Year Limited Warranty.
- Failure to adhere to installation protocol will void the Warranty.
- 7. SIMPLIPHI TECHNICAL SUPPORT
- For technical support related to your PHI Battery (or other SimpliPhi Power products), please contact us directly at:
- 805.640.6700
- techsupport@simpliphipower.com
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 18 |
Homeowners who wish to include a grid connection, generator, and Smart Load functionality can install a
transfer switch allowing for either grid or generator to connect to the Sol-Arkโs Grid Input. This frees up the
Sol-Arkโs Generator Input to be used as an output for Smart Loads (see the following Smart Loads section for
more details).
In an AC Coupled system setup that includes a generator, using a transfer switch for a grid-or-generator
connection to the Sol-Arkโs Grid Input also frees up the Sol-Ark Generator Input for connection to the AC
Coupled solar PV array.
If the system includes both a generator and a grid connection, limiter sensors are required. While smaller
generators (less than 10 kW) can be wired to the Sol-Arkโs Generator Input, Sol-Ark recommends wiring larger
generators to a whole home transfer switch instead of using the inverterโs Generator Input.
Smart Load
The Smart Load feature allows the homeowner to run higher power non-essential appliances (hot water,
dehumidifier, heat pump, irrigation pump, etc.) on solar when excess solar power is available. This setup
involves connecting these higher power non-essential loads to the Sol-Arkโs Generator Input. To partially
protect the batteries against over-discharge, set the
Smart Load Off Batt and Smart Load ON Batt parameters
to the batteriesโ acceptable SoC percentage range while in this mode. However, note that no programmable
parameter exists to regulate the batteriesโ over-discharge from a current perspective.
For example, an off-grid system with home loads totaling a maximum instantaneous power draw of 8 kW might
include 5 PHI 3.8 batteries, with a maximum combined continuous power output of 9.6 kW
DC
/ 9.168 kW
AC
.
With both the
Smart Load and Limited to Load modes enabled and the Smart Load ON Batt parameter set to
100% SoC, the Sol-Ark will begin powering the Smart Loads (in addition to all the home loads) when the
batteries are at 100% SoC. If the Smart Load power draw exceeds 9.168 kW
AC
, (38.2 Amps at 240VAC), the
batteries will then be operating beyond their maximum continuous power output capabilities. While the
batteries have a maximum surge discharge capability of 60 Amps DC per battery (15.36 kW
DC
/ 14.669 kW
AC
for the 5-battery bank), the batteries cannot surge at this power level for more than 10 minutes. A Smart Load
drawing more than 9.168 kW
AC
for more than 10 minutes will very likely result in the batteriesโ SoC level
reaching the
Smart Load OFF Batt parameter, if it is set to 95%. However, feel free to reach out SimpliPhi
Power Technical Support (
TechSupport@SimpliPhiPower.com) if the Smart Load feature will be used and
battery bank sizing clarification according to Smart Load-specific loads needs to be clarified.
Note that in a grid-connected system that utilizes the Smart Load feature, the Wattage value to the right of the
Smart Load ON Batt parameter in the Smart Load menu tab (see Figure 5) represents the minimum power
required of the solar PV array before the Smart Loads are powered. Therefore, that Solar PV Wattage value
can be added to the battery bankโs maximum output power rating when comparing maximum available solar
and battery power available, against the Smart Load power draw: ๎ดต๎ต๎ดฝ๎ต๎ต ๎ดฎ๎ต๎ดฝ๎ต ๎ดฆ๎ต๎ดฝ๎ต
(
๎ต๎ดน
)
โค
๎ดต๎ต๎ต๎ดฝ๎ต ๎ดฒ๎ดธ
(
๎ต๎ดน
)
+ ๎ดค๎ดฝ๎ต๎ต๎ต๎ต๎ต๎ต ๎ดค๎ดฝ๎ต๎ต ๎ดฏ๎ดฃ๎ดบ ๎ดฑ๎ต๎ต๎ต๎ต๎ต ๎ดฒ๎ต๎ต๎ต๎ต (๎ต๎ดน).
CAUTION: Smart Loadsโ maximum power draw cannot exceed the Generator Input breakerโs
40 Amp / 240VAC rating.