AmpliPHI Sol-Ark Integration Guide
Table Of Contents
- 1. introduction
- 2. PHI battery bank-to-inverter connection
- Wire the PHI Battery bank to the Sol-Ark according to the PHI Battery Installation Manual, not according to the Sol-Ark Manual:
- Figure 1 β Sol-Ark to Battery Connection
- It is acceptable but not required to use the ferrite choke on the positive and negative DC busbar-to-inverter leads (see Figure 1 above).
- SimpliPhi and Sol-Ark recommend against using the 100 Ohm resistor included with the Sol-Ark equipment to charge the Sol-Arkβs capacitors when connecting the PHI Batteries for the first time (as described in the Sol-Ark Install Guide Ownerβs Manual).
- Do not install the Battery Temperature Sensor. The PHI Batteries require no temperature compensation.
- 3. Battery bank sizing
- A properly sized PHI battery bank is sized to prevent over-discharge and over-charge from accompanying equipment. While the programming features of the Sol-Ark allow for battery discharging and charging according to specifically set parameters (refer ...
- Therefore, the PHI battery bank should still be sized to protect against over-discharge. In the case of an AC Coupled system setup, the PHI battery bank should also be sized to protect against over-charge from the solar photovoltaic (PV) array. In a D...
- Discharge Example: ,π©-#π°ππ.β₯,,π°ππ-ππΎ.Γ·,π°ππ-πππ.-,π©ππ-ππΎ..
- Charge Example: ,π©-#π·π½.β₯,,π·π½-ππΎ.-π.πΓ,π©ππ-ππΎ..
- ο· AC Coupled Solar PV Array is rated at 8 kW
- ο· PHI 3.8 kWh-51.2Vnom battery has a maximum continuous charge rate of 1.92 kWDC
- ,π©-#π·π½.β₯,,π-ππΎ.-π.πΓ,π.ππ-ππΎ..=π.π
- A properly sized PHI battery bank based on the maximum charge from the AC Coupled solar PV array has a minimum of 6 batteries. This ensures that the battery bank does not over-charge from the AC Coupled solar PV.
- When comparing the same system using both the discharge and charge calculations for sizing the PHI battery bank, the minimum number of batteries in the bank should be the greater of the two results. For instance, when examining the discharge calculati...
- While the PHI battery bankβs charge rate in a DC Coupled system can be limited via Sol-Ark programming (Max A Charge), consider the PHI battery bankβs maximum continuous charge rate in the systemβs design.
- Charge Example: ,π©-#π·π½.β₯,,π·π½-ππΎ.Γ,π°ππ-πππ.-,π©ππ-ππΎ..
- ο· DC Coupled Solar PV Array is rated at 8 kW
- ο· Sol-Ark PV-to-Battery efficiency is 97.5%
- ο· PHI 3.8 kWh-51.2Vnom battery has a maximum continuous charge rate of 1.92 kWDC
- ,π©-#π·π½.β₯,,π-ππΎ.Γ,π.πππ-πππ.-,π.ππ-ππΎ..=π.ππ
- A PHI battery bank utilizing the entire DC Coupled solar PV output potential has 5 batteries. However, programming the Max A Charge in the Sol-Ark to 150 A (4 Γ 37.5 ADC) would prevent the over-charging of a battery bank that includes only 4 batteries...
- Homeowners with little to no loads on during the day (while solar power production is at its peak) might consider sizing a larger PHI battery bank to take advantage of the entire solar PV output potential for battery charging. Homeowners that consiste...
- 4. program settings for phi batteries
- 5. USE CASES & Application notes
- Sol-Ark equipment includes many advanced programming features and a variety of modes (more than one mode can be used simultaneously). This section of the Guide will outline the system programming and setup basics for common use cases. However, refer a...
- 6. SPECIFICATIONS & WARRANTY
- For your reference:
- ο· See PHI 3.8 kWh Specifications Sheet.
- ο· See PHI 2.9 kWh Specifications Sheet.
- ο· See PHI Battery 10 Year Limited Warranty.
- Failure to adhere to installation protocol will void the Warranty.
- 7. SIMPLIPHI TECHNICAL SUPPORT
- For technical support related to your PHI Battery (or other SimpliPhi Power products), please contact us directly at:
- 805.640.6700
- techsupport@simpliphipower.com
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 15 |
Checking the Limited power to Home box in the Limiter tab of the Sol-Arkβs Grid Setup / Grid Param menu
allows for all loads* (on both the critical loads sub-panel and the main house breaker panel) to be powered using
the connected solar PV and/or batteries. The Sol-Ark prioritizes powering these loads from solar PV first (if
available), then (2) grid, (3) generator, and (4) batteries. To prioritize the batteriesβ use over the grid or
generator during specific set times, also use the
Time of Use Selling mode.
*While the Limited to Home mode allows for all loads to be powered using solar PV and/or batteries, the Sol-
Ark prioritizes powering loads on the critical loads sub-panel first, and loads on the main house breaker panel
are offset by solar (and/or batteries, during Time of Use Selling mode times) as much as possible. If the loadsβ
draw exceeds the available power from the solar PV array and (with
Time of Use Selling mode also in play) the
batteries have also discharged to their minimum programmed SoC percentage level, the Sol-Ark will then
resort to powering loads using grid power.
CAUTION: In Limited to Home mode, limiter sensors are required to ensure that the homeβs
main breaker panel circuits are powered without exporting energy to the grid.
Limited to Load
Checking the Limited power to load box in the Limiter tab of the Sol-Arkβs Grid Setup / Grid Param menu
discharges the battery to power the critical loads sub-panelβs loads. The
Limited to Load mode does not allow
for any solar or battery energy to power the main house breaker panel and it does not allow for any solar or
battery energy to be exported to the grid.
Figure 6 β Limiter Tab in Grid Setup menu