AmpliPHI Sol-Ark Integration Guide

Table Of Contents
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 13 |
Time
sets the time at which the batteries discharge to power both the critical loads sub-panel
and the main house breaker panel (limiter sensors required)
power (W)
sets the maximum amount of power discharged from the batteries during the set time
do not exceed the Wattage values listed in Tables 2 or 3 above
Batt
the percentage SoC to which the batteries discharge during the set time
20% 10% 0%
Grid Charge
check this box to allow for grid-to-battery charging during the set time
GEN
check this box to allow for gen-to-battery charging during the set time
> Sell Control Tab
80% DoD
90% DoD
100% DoD
General Standard
check this box when a generator is wired to the Grid Input
or to use the
Protect Param
settings listed in the
Grid Input
tab
UL 1741 & IEEE 1547
check this box for grid sell compliant functionality (default)
CA Rule 21
check this box for compliance with CA Rule 21
UL 1741SA
check this box for compliance with HECO Rule 14H and/or PREPA
GEN connect to Grid input
check this box when a generator is wired to the Grid Input
> Grid Input Tab
Grid Frequency
select 50 Hz or 60 Hz
Grid Type
select 120/240V split phase (North America),
or contact SimpliPhi to special-order 220V single phase or 120/208V 3 phase
Protect Param
leave as default values when UL 1741 & IEEE 1547 are enabled
frequency values may change when a generator is wired to the Grid Input
> FreqVolt tab
refer to the Sol-Ark Manual for Puerto Rico or Kauai-specific settings
AC Coupled
In an AC Coupled system setup, the grid-tie inverter(s) output – string or micro-inverters – is wired to the Sol-
Ark’s Generator Input (40A double-pole breaker) and the
For Micro inverter input box in the Smart Load tab of
the
Battery Setup menu must be checked:
Figure 5 – Smart Load Tab in Batt Setup menu