AmpliPHI Sol-Ark Integration Guide

Table Of Contents
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 9 |
Start V
Use Start % instead of Start V when using
Batt % Charged instead of Batt V Charged (in the Batt tab)
Start %
3
21% 11% 1%
A
1,4
37.5 ADC per PHI 3.8 battery (20 ADC per battery for reduced stress)
Gen Charge / Grid Charge
5
Check the Gen Charge box when a generator is connected to the Gen Input breaker.
Check the Grid Charge box when a generator is connected to the Grid Input breaker,
or when a grid connection is utilized to charge the batteries.
Float V
54 V
Absorption V
6
56 V
Equalization V
7
56 V
30 days
1 hour
> Discharge Tab
80% DoD (recommended)
90% DoD
100% DoD
Shutdown
20% (50.2 V) 10% (49.5 V) 0% (48 V)
Low Batt
30% (50.5 V) 20% (50.2 V) 10% (49.5 V)
Restart
97% (52 V) 97% (52 V) 97% (52 V)
Batt Resistance
Resistance mOhms = 96 Γ· (4 Γ— PHI 3.8 battery quantity)
Resistance mOhms = 96 Γ· (3 Γ— PHI 2.9 battery quantity)
Batt Charge Efficiency
99%
> Smart Load Tab
Use Gen input as load output
check this box if the Smart Load feature applies (refer to Section 5 of this Guide)
Smart Load OFF Batt
8
95% (51.7 V)
Smart Load ON Batt
9
100% (52.5 V)
Wattage value is used in grid-connected systems only. This value represents the minimum power
required of the solar array before the Smart Loads are powered.
For Micro inverter input
check this box for AC coupled systems
Smart Load OFF Batt
10
100% (52.5 V)
Smart Load ON Batt
11
30 – 95%