AmpliPHI Sol-Ark Integration Guide

SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
|
7
|
© SIMPLIPHI POWER
Figure 5: AmpliPHI’s Networking Connections to Sol-Ark Equipment
3.0 Battery Bank Sizing
3.1All Systems
AmpliPHI batteries in DC Coupled or AC Coupled systems should be sized according to the connected loads’
energy (kWh) and power (kW) requirements. While as few as one AmpliPHI battery may be paired with either
Sol-Ark-8K or Sol-Ark-12K equipment without voiding the battery warranty, consider that the AmpliPHI
battery is rated according to the specifications in the table below, and that without a backup AC power source,
loads that exceed the battery bank’s total capacity or power rating will result in the entire system shutting
down. Specifically, when operating in off-grid mode, the Sol-Ark shuts down when the current discharged from
the battery bank to the loads exceeds 120% of the Sol-Ark’s
Max A Discharge parameter value for 10 seconds.
Battery bank-to-inverter
networking connection
Terminator plugs at
either end of the
battery “daisy-chain”
bank-to-inverter
networking connection