AmpliPHI Sol-Ark Integration Guide
Table Of Contents
- 1.0 – Introduction
- 2.0 – Battery Bank-to-Inverter Connection
- 3.0 – Battery Bank Sizing
- AmpliPHI 3.8 Battery
- 3.8 kWh DC @ 100% DoD
- Rated kWh Capacity per Battery
- 3.04 kWh DC @ 80% DoD (recommended)
- 37.5 Amps DC (1.9 kW DC)
- MAX Continuous Discharge Rate
- 4.0 – Program Settings for PHI Batteries
- 5.0 – Use Cases & Application Notes
- 6.0 – Specifications & Warranty
- 7.0 – SimpliPhi Power Technical Support
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
|
16
|
© SIMPLIPHI POWER
5.0 – Use Cases & Application Notes
Sol-Ark equipment includes many advanced programming features and a variety of modes (more than one
mode can be used simultaneously). This section of the Guide will outline the system programming and setup
basics for common use cases. However, refer also to the Sol-Ark Manual for all installation requirements
relevant to the application at hand.
Table 3 – Sol-Ark Grid Settings
System Setup > Grid Setup
80% DoD 90% DoD 100% DoD
(10k cycle warranty) (5k cycle warranty) (3.5k cycle warranty)
> Limiter Tab
Grid Sell
check this box when exporting solar PV power to the grid
(Net Energy Metering agreement required)
set the numerical value to the maximum number of exporting Watts
Limited Power to Home
check this box when powering both the critical loads sub-panel and
the main house breaker panel using solar and/or battery,
without exporting energy to the grid (limiter sensors required)
Limited power to load check this box when powering the critical loads sub-panel using solar and/or battery
Time of Use Selling
check this box when discharging the batteries during set times
(either the Grid Sell or Limited Power to Home box must also be checked)
Time
sets the time at which the batteries discharge to power both the critical loads sub-panel and the main
house breaker panel (limiter sensors required)
power (W)
sets the maximum amount of power discharged from the batteries during the set time
do not exceed the Wattage values listed in Tables 2 or 3 above
Batt
the percentage SoC to which the batteries discharge during the set time
20% 10% 0%
Grid Charge check this box to allow for grid-to-battery charging during the set time
GEN check this box to allow for gen-to-battery charging during the set time
> Sell Control Tab 80% DoD 90% DoD 100% DoD
General Standard
check this box when a generator is wired to the Grid Input
or to use the Protect Param settings listed in the Grid Input tab
UL 1741 & IEEE 1547 check this box for grid sell compliant functionality (default)
CA Rule 21 check this box for compliance with CA Rule 21
UL 1741SA check this box for compliance with HECO Rule 14H and/or PREPA
GEN connect to Grid input check this box when a generator is wired to the Grid Input
> Grid Input Tab
Grid Frequency select 50 Hz or 60 Hz
Grid Type
select 120/240V split phase (North America),
or contact SimpliPhi to special-order 220V single phase or 120/208V 3 phase
Protect Param
leave as default values when UL 1741 & IEEE 1547 are enabled
frequency values may change when a generator is wired to the Grid Input
> FreqVolt tab refer to the Sol-Ark Manual for Puerto Rico or Kauai-specific settings
REV202105181844