Specifications
9
®
Note: When the older generations of 65UV5-1000 or -1000E scanners are used for a Class 1, Div. 2
application, the cable gland MUST be removed and replaced with P/N 129-149, liquid tight cable
gland, so that liquid tight flexible conduit (Anaconda Sealtight ® 1/2" Type H.T.V.A or equivalent,
available at any electrical supply outlet) can be inserted over the existing cable. The newer genera-
tion 65UV5-1004 and 1004E utilize a special cable that is approved for use in a Class 1, Div. 2 area
without the use of the flexible conduit.
SCANNER WIRING - CEX VERSIONS
CEX models are wired directly and have a terminal rail to connect which is located within the CEX
housing. Suitable EX glands must be used to terminate the cable at the housing.
To reduce electrical noise interference, take precautions to keep the scanner cable away from any
high inductive wiring associated with high inductive loads or high voltage, high energy spark igni-
tion systems.
FIGURE 9. WIRING OF SIMPLICITY MODEL 65UV5-1004 “CEX” SCANNERS
Note: 4-20mA negative connection should connect to the power supply negative wire (white).
TERMINAL FUNCTION INTERNAL FACTORY WIRE COLOR
1 FLAME RELAY COM BLACK
2 FLAME RELAY NC RED BLOCK 1
3 SAFETY RELAY NC BLUE
4 FLAME RELAY NO YELLOW
5 24VDC IN WHITE (-)
6 24VDC IN BROWN (+) BLOCK 2
7 GROUND GREEN
8 4-20 OUT ORANGE
ALTERNATE LIQUID
TIGHT CONNECTION
WARNING: Unit should be electrically protected by external fuses (see Fig. 7 and Fig. 8 for
rating) to prevent damage to unit in case of a short or overload.