Specifications
8
®
FIGURE 7. SCANNER WIRING FOR 1000 AND 1000E SCANNER VERSIONS
FIGURE 8. SCANNER WIRING FOR 1004 AND 1004E SCANNER VERSIONS
65UV5-1000 (E) SCANNER
FLAME
SAFETY GROUND SCREW
24VDC
INPUT
BLACK
BLACK
RED
RED
24VDC SUPPLY
(POLARITY NOT IMPORTANT)
TO BURNER MANAGEMENT
SYSTEM
RELAY
SAFETY
RELAY
1 AMP SLOW BLOW*
3 AMP SLOW BLOW*
*EXTERNAL FUSES
SCANNER MUST BE CONNECTED TO GROUND
BLUE
ORANGE
FLAME
RELAY
OUTPUT
INTERNAL
GROUND
CONTACT
24 VDC
INPUT
POWER
BLACK
WHITE -
RED
BROWN +
GREEN
YELLOW
ANALOG
OUTPUT
FAULT
RELAY
EARTH
GROUND
65UV5- 1004, -1004E SCANNER
INPUT
SUPPLY
24 VDC
(NOTE 1)
SUPPLY 5 VDC
TO 230 VAC
(NOTE 2)
(1 AMP SLOW BLOW)
(3 AMP SLOW BLOW)
VOLTAGE = NO
FAULT CONDITION
(NOTE 3)
FLAME OFF
FLAME ON
(NOTE4)
(NOTE 5)
FLAME STRENGTH
EARTH
GROUND
*
*
*
EXTERNAL FUSE
(-)
(+)
CABLE COLOR CODES AND DESCRIPTIONS
BLUE = Relay voltage input (5 VDC to 230 VAC, 1mA to 2000mA) fused
BLACK = Safety Relay voltage output (voltage output when no error)
RED = No flame present ( voltage output when no flame)
YELLOW = Flame is present (voltage output when flame is present)
ORANGE = 4-20 mA flame strength output (not safety critical)
GREEN = EARTH GROUND
BROWN = 24 Volt supply (+)
WHITE + 24 Volt supply return (-)
NOTES:
1. Fireye recommends the use of power supply 60-2685 -2, -4
2. Suitable signal voltage provided by BMS
3. Fault relay is closed when scanner is in no fault condition
4. Flame OFF/OPEN when flame is present
5. Flame on CLOSE when flame is present
4 TO 20mA