MAINTENANCE
1. The control and scanner should be powered at all times (except for repair, cleaning or replace-
ment) to reduce any harmful effects of atmospheric humidity.
2. The scanner and sight pipe must be kept clean to prevent overheating and assure optical quali-
ties.
3. When replacing or cleaning the UV tube, note the position of the tube pins. They are mounted
on a rectangular base so that the tube can only be inserted into the socket with the electrodes
broadside to the shutter window.
4. Clean the quartz lens and tube with glass detergent or glass cleaning agents which contain no
abrasives. After cleaning, remove all cleaning films with a soft lint-free cloth. (Some cleaning
films may reduce or filter UV).
5. Use original FIREYE parts to maintain optimum operation.
Recommended spare parts:
Part NumberDescription
4-290-1 UV Tube
61-6974 Shutter Assembly with Lens
002608-001 Flange Gasket
92-48 Quartz window (Part of Union 60-1199)
FIREYE original equipment factory replacement parts are available at various sub-assembly levels.
Start an adjacent burner and vary its firing rate under normal airflow conditions. Make certain that
the main flame scanner on the burner not in service does not respond to adjacent burner flame. Read
just sighting if necessary.
ALTERNATE PURGE
AIR SUPPLY
1” UNION
3/4” PLUG
OR PURGE
AIR SUPPLY
FIELD
OF
VIEW
1” SWIVEL MOUNT
FIELD OF VIEW
BALL
SWIVEL MOUNT
ORIFICE ORIFICE
RETAINER
CAUTION: DISCONNECT OR SHUT OFF ELECTRIC POWER WHEN WORKING
ON SCANNER.