Specifications

NOTE:
The 760-A Aquaswitch is not designed to operate with a Cell cable
length that exceeds 100' (30 meters).
3 If at all possible, mount the Controller at eye level for
viewing convenience.
2.2.1 SURFACE MOUNTING
NOTE:
Surface mounting will require two (2) user supplied 1/4 20
mounting screws See, Fig. 2-1 for hole drilling locations. For ease
of surface mounting, a surface mounting plate is available.
Order Part No.: SMP50 for Aquaswitch
SMP60 for 760-A Aquaswitch
STEP 1 Select your site location. Mark and drill the two (2) required
mounting holes.
STEP 2 lace the mounting threads in alignment with the surface
mounting holes.
STEP 3 Insert and securely fasten the two (2)1/4':20 mounting
screws.
2.2.2 PANEL MOUNTING INSTALLATION
A panel mounting fastening kit is provided with all Aquaswitch/
760-A Aquaswitch enclosures. Panel mounting will require the use
of the fastening kit’s two (2) 4-40 mounting screws/nuts or two
(2) #4 x 1/2 sheet metal screws. See Fig. 2-1 for panel cutout
dimensions.
STEP 1 Select your site location, mark the appropriate pane I cut
out and complete the necessary panel cut.
STEP 2 Carefully unfasten and separate the front panel from its
enclosure.
STEP 3 Disconnect all panel cable(s)/wires from the enclosure’s
component board(s).
STEP 4 Slide the enclosure through the panel cutout until its ange
contacts the panel.
STEP 5 Insert mounting screws through the ange mounting holes
and tightly secure.
STEP 6 Reconnect all panel cable(s)/wires. (See Fig. 4-1)
2.2.3 HP SOLENOID PILOT VALVE INSTALLATION
STEP 1 Insert the pilot valve unit so that the systems’ INFLOW
source and OUTFLOW process piping connecting ends
are inserted into the valve as shown in Fig. 2-2.
STEP 2 Repeat STEP 1 until all appropriate pilot valve units have
been installed.
NOTE:
The number of pilot valves used will be based upon the user’s
desired application.
2.2.4 CELL INSTALLATION (MODEL 760-A ONLY)
NOTE:
Fig. 2-3 illustrates how to properly assemble and install the CS10
Cell assembly into a “T” type mounting xture. Improper assembly
could result in damage to equipment and/or property.
A CS10 Cell’s mounting orientation must provide a continuous
and adequate circulation ow to prevent the trapping of air bubbles
within the Cell’s electrode area. Failure to do so will result in
conditions that will prevent the cell from functioning properly.
STEP 1 Verify that the Cell components are properly
assembled.
STEP 2 Insert the Cell assembly into the “T” mounting xture as
shown in Fig. 2-3 and tightly secure.
4