Specifications

6-2 888-2500-001 5/2/2013
WARNING: Disconnect primary power prior to servicing.
DAX-1/DAX-3
Section 6 Troubleshooting
6.2.1 Fault Log
Certain faults are listed for quick reference in Table 6-1 on page 6-27. The most recent
fault will be displayed as the topmost listing.
To assist in determining the possible causes of a malfunction, the DAX transmitter
stores fault occurrences including the elapsed time since they occurred.
The DAX controller stores 75 fault listings and operates with the first in first out (FIFO)
concept of data repletion. In other words, the fault log will only contain the last 75
faults. It is highly unlikely that there would ever be 75 faults to be listed, but it is
possible if the fault log had not been reset for a very long period and/or there was many
nuisance fault trips, that early faults would be ’pushed out’ by the more recent faults -
never totalling more than 75.
NOTE:
Upon loss of AC power to the DAX controller after or during a fault condition,
fault time information may be incorrect.
6.2.1.1 Viewing the Fault Log
Viewing the Fault Log on the GUI screen can be accomplished y the following
procedure:
STEP 1 Pressing the INFO button takes you to below screen
Figure 6-1 INFO Screen
STEP 2 Select FAULT SUBMENU using the UP or DOWN buttons
STEP 3 Press ENTER to bring up below screen
Figure 6-2 Fault Log Screen