Input Power Requirements Voltage Range Frequency Maximum Current
AC Input, 120 VAC base models 102 to 132 VAC 60 Hz 2 A
AC Input, 240 VAC base models 204 to 264 VAC 50/60 Hz 1 A
AC Input with 120 VAC expansion power supply 102 to 132 VAC 60 Hz 4 A
AC Input with 240 VAC expansion power supply 204 to 264 VAC 50/60 Hz 2 A
Environmental
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
Output Ratings
Standard Power Supply Output 4 A total @ nominal 28 VDC
Auxiliary Power Tap
1/2 A maximum of standard power
supply voltage
Expansion Power Supply Output * Additional 4 A @ nominal 28 VDC
Suppression Release Power Supply Output * Additional 4 A @ 24 VDC ±10%
Output switches to battery
backup during mains failure
or brownout conditions
* Each power supply provides two output taps of 2 A each.
Current Ratings for Optional Modules and Remote LCD Annunciator
Model
Module
Supervisory
Current
Alarm
Current
4010-9810 DACT (Common Event Reporting) 40 mA 40 mA
4010-9816 DACT (Point Reporting) 40 mA 40 mA
4010-9821 4120 Network, wired communications 125 mA 125 mA
4010-9817 4120 Network Modular, add media cards separately 24 mA 24 mA
4010-9818 4120 Network Wired Media 47 mA 47 mA
4010-9819 4120 Network Fiber Optic Media 36 mA 36 mA
4010-9811 Dual RS-232 75 mA 75 mA
4010-9812 Single RS-232 with Service Modem 100 mA 100 mA
4010-9806 Dual Class A NAC Adapter 0 mA 0 mA
4010-9809 Dual Circuit City Connect 20 mA 36 mA
4010-9829 Dual Circuit City Connect w/o disconnect switches 20 mA 36 mA
4606-9101 Remote LCD Annunciator (refer to data sheet S4606-0001) 65 mA 140 mA
System Current (supplied separate from power supply output)
Base System with:
Supervisory
Current**
Alarm
Current**
no IDNet devices 195 mA 295 mA
50 IDNet devices 230 mA 330 mA
100 IDNet devices 265 mA 365 mA
150 IDNet devices 300 mA 400 mA
200 IDNet devices 335 mA 435 mA
250 IDNet devices 370 mA 470 mA
** Current Calculation Information:
1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC
loads and all auxiliary loads.