System information

Standard Panel Features
N2 Communications for Serial Annunciator
Control. Control for up to 6 remote Simplex
Annunciator products including 24 Point I/O Module, and
LCD Annunciator. Includes extensive troubleshooting
diagnostics.
Access Port. RS-232 service port for connecting PC
tools for service diagnostics and for programming the
CPU Flash EPROM memory.
IDNet Addressable Communications Channel.
Addressable channel provides communications for up to
250 remote addressable devices, including TrueAlarm
analog sensors and isolator bases (see descriptions on
page 3).
Four NACs. Class B output is standard, rated for 2 A @
24 VDC nominal, with solid state current protection.
Class A operation is optional with the addition of an
adapter module.
NAC operation can be selected for “on-until-Silence” or
“on-until-Reset,” and can be Temporal pattern, 60 or
120 bpm March Time pattern, or continuous. Each NAC
is also individually selectable to control Simplex
synchronized visible notification appliances and to control
audible notification appliances using SmartSync
control, allowing separate audible and visible appliance
operation using a common 2-wire circuit. (Contact
Simplex for more information.)
Two Auxiliary Output Circuits. Operation is
programmable for trouble, alarm, supervisory, or other
fire response functions. Output is one form “C” dry
contact each, rated 2 A @ 24 VDC. An optional relay kit
is available for switching up to 1/2 A at 120 VAC.
Power Supply. Standard output is 4 A @ 28 VDC,
filtered, non-regulated. Internal system power is provided
separately, allowing the 4 A to be available for NAC and
auxiliary power tap functions. Over-current protection is
solid state and self-resetting.
Auxiliary Power Tap. Provides up to 1/2 A of the
standard power supply voltage, over-current protected.
Battery Charger. Capable of charging up to 25 Ah
sealed lead-acid batteries (4010 cabinet mounted). A
recharge time of 24 hours is typical with stable 120 VAC
input. For applications requiring larger batteries, external
charger/cabinet assemblies are available.
A depleted battery cutout feature is front panel selectable
to advise and/or to reduce current when battery voltage is
low.
Optional Expansion Slot Modules
(The 4010 is available with a Simplex 4120 Network
Interface. 4010 points can be declared “public.”)
4120 Network Interface, Fixed Media. Available for
wired applications.
4120 Network Interface, Modular Media. Available
for wired connections or fiber optic. Require separate
media modules. May be both wired, both fiber optic, or
one of each.
DACT, Point Reporting Module. Provides serial
output information that can send location details to a
remote receiving station.
DACT, Event Reporting Module. For applications
where simple event status information is required (Alarm,
Trouble, Supervisory, and AC power failure).
Dual RS-232 Module. Available for interfacing to
printers or a maintenance terminal.
Single RS-232 Module with Service Modem
Connection. Provides one port dedicated for connection
to a printer, and a second port dedicated for dial-in from a
service terminal, typically located off-site. With an off-
site terminal, programming changes and system
diagnostics can be performed remotely, reducing service
time for repair or reprogram. Security is maintained by
password protection.
Optional Chassis Mount Modules
Standard 4 A Expansion Module. Provides two taps
of 2 A each, 28 VDC, filtered, non-regulated, similar to
the standard power supply capacity.
Suppression Release Power Supply. This module
provides two taps of 2 A each, regulated at 24 VDC
± 10%. Also included is a suppression release appliqué.
(This module may also be used for other applications
requiring regulated voltage.)
Battery Meter Module. Provides ammeter and
voltmeter for power supply monitoring.
Dual Circuit Class A NAC Adapter Module. Mounts
on the main 4010 printed circuit assembly and provides
the additional circuitry needed for Class A operation.
Dual Circuit City Connect Module. Provides the
interface required for direct wired reporting to
conventional city connection circuits. (Available with or
without disconnect switches.)
Expansion Power Distribution Module. This
module provides two additional termination points for the
1/2 A auxiliary power output, or for one tap of the
expansion power supply.
External N2 Communications Modules
Up to six modules may be connected to the Simplex N2
serial communications bus.
4606-9101 LCD Annunciators provide remote
acknowledge, reset, and alphanumeric status display.
(Refer to data sheet S4606-0001.)
4605 Series 24 Point I/O Modules are available for
remote mounting and provide 24 points that can be
programmed as either general purpose switch inputs or
system controlled outputs. Typical applications are for
remote annunciators and monitoring and control of other
related processes. (Refer to data sheet S4010-0002.)
Simplex Time Recorder Co. 5 S4010-0001-4 4/00